2013-06-10 15:38:32CHANGE OF OCCUPANCY TO RESIDENTIAL (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010
 FBC-ENERGY CONSERVATION.
 ***NOTE; COORDINATE WALLL AND CEILING INSULATION WITH
 PLANS.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 REQUIRED. THERE IS A CHANGE OF USE. THEREFORE, PALM
 BEACH COUNTY NEEDS TO REVIEW PLANS. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 THIS IS REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 3- A) TENANT SEPARATION NEEDS TO COMPLY WITH SEC.
 R302.3. WALL ASSEMBLY NEEDS TO EXTEND TO THE UNDERSIDE
 OF THE ROOF SHEATHING. REVISE TENANT SEPARATION DETAIL
 ON SHEET 2. ALSO, PROVIDE ONLY THE INFORMATION THAT
 APPLIES TO THIS PROJECT. THERE IS INFORMATION ON THIS
 DETAIL THAT DOESN'T APPLY TO THIS PROJECT. COORDINATE
 WITH WALL LEGEND ON SHEET 1.
  
 B) SHEET 1: CLARIFY WHERE IS THE "TYPICAL DETAIL ALL
 OPENINGS FILL IN W. 2X8 SYP FRAMING" GOING TO BE
 INSTALLED?. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 4- REVISE ONE HOUR ASSEMBLY SPECIFIED ON THE TENANT
 SEPARATION DETAIL ON SHEET 2. NEED TO SPECIFY ASSEMBLY
 THAT INCLUDES THE 3" SOUND INSULATION AND R11 BATT
 INSULATION SHOWN ON THE DETAIL. THE ASSEMBLY NEEDS TO
 BE TESTED IN ACCORDANCE WITH ASTM E 119 OR UL 263 AS
 REQUIRED BY SEC. R302.3 OF 2010 FBC-RESIDENTIAL. ALSO,
 CLARIFY SIZE OF WALL 2X4 WALL OR 2X6 WALL. COORDINATE
 WITH SPECIFIED REVISED ASSEMBLY. WALL LEGEND ON SHEET 1
 SAYS 5-5/8" PARTITION, WHILE TENANT SEPARATION DETAIL
 SPECIFIES 2X4. REVISE AS REQUIRED.
  
 5- SHEET 1: NEED TO PROVIDE ATTIC ACCESS FOR EACH UNIT.
 SEC. R807 OF 2010 FBC-RESIDENTIAL.
  
 6- A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED
 BY DCA RULE 9N-3 FOR ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS/DETAILS. PROVIDE ONLY THE COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 B) CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR WINDOW
 MULLIONS. PLANS DON'T SHOW ANY WINDOW MULLION. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- SPECIFY SIZE OF EGRESS WINDOW ON BEDROOM LOCATED ON
 UNIT #2 ON THE NORTH EAST CORNER. SEC. R310 OF 2010
 FBC-RESIDENTIAL.
  
 8- SHEET 3. THIS IS NOT A LEVEL II ALTERATION. THIS IS
 A CHANGE OF OCCUPANCY. SEC. 406 OF 2010 FBC-EXISTING
 BUILDING. REVISE NOTE AS REQUIRED.
  
 9- SHEET D1: PROVIDE ONLY THE DETAILS AND
 SPECIFICATIONS THAT APPLY TO THIS JOB. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  