2013-06-12 16:08:35CHANGE OF OCCUPANCY TO RESIDENTIAL (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010
 FBC-ENERGY CONSERVATION.
 ***NOTE; COORDINATE WALLL AND CEILING INSULATION WITH
 PLANS.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 REQUIRED. THERE IS A CHANGE OF USE. THEREFORE, PALM
 BEACH COUNTY NEEDS TO REVIEW PLANS. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 THIS IS REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 3- A) TENANT SEPARATION NEEDS TO COMPLY WITH SEC.
 R302.3. WALL ASSEMBLY NEEDS TO EXTEND TO THE UNDERSIDE
 OF THE ROOF SHEATHING. REVISE TENANT SEPARATION DETAIL
 ON SHEET 2. ALSO, PROVIDE ONLY THE INFORMATION THAT
 APPLIES TO THIS PROJECT. THERE IS INFORMATION ON THIS
 DETAIL THAT DOESN'T APPLY TO THIS PROJECT. COORDINATE
 WITH WALL LEGEND ON SHEET 1.
  
 ****NOTE: THERE IS GOING TO BE A PROBLEM TO COMPLY WITH
 THIS SECTION IF THE ROOF TRUSSES DON'T ALLOW THE WALL
 TO GO ALL THE WAY UP TO THE UNDERSIDE OF THE ROOF
 SHEATHING. PLANS MAY NEED TO BE REVISED. SEE TENANT
 SEPARATION WALL SEGMENT BETWEEN UNIT #2 WALK IN CLOSET
 AND UNIT #1 KITCHEN AREA.
  
  
 B) SHEET 1: CLARIFY WHERE IS THE "TYPICAL DETAIL ALL
 OPENINGS FILL IN W. 2X8 SYP FRAMING" GOING TO BE
 INSTALLED?. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 4- REVISE ONE HOUR ASSEMBLY SPECIFIED ON THE TENANT
 SEPARATION DETAIL ON SHEET 2. NEED TO SPECIFY ASSEMBLY
 THAT INCLUDES THE 3" SOUND INSULATION AND R11 BATT
 INSULATION SHOWN ON THE DETAIL. THE ASSEMBLY NEEDS TO
 BE TESTED IN ACCORDANCE WITH ASTM E 119 OR UL 263 AS
 REQUIRED BY SEC. R302.3 OF 2010 FBC-RESIDENTIAL. ALSO,
 CLARIFY SIZE OF WALL 2X4 WALL OR 2X6 WALL. COORDINATE
 WITH SPECIFIED REVISED ASSEMBLY. ALSO, WALL LEGEND ON
 SHEET 1 SAYS 5-5/8" PARTITION, WHILE TENANT SEPARATION
 DETAIL SPECIFIES 2X4. REVISE AS REQUIRED.
  
 5- SHEET 1: CLARIFY ATTIC ACCESS ON UNIT #2. THERE ARE
 TWO SHOWN. ATTIC ACCESS SHOWN ON THE WALK IN CLOSET IS
 NOT READILY ACCESSIBLE. OTHER ONE LOCATED IN THE
 BEDROOM IS OK.
 SEC. R807 OF 2010 FBC-RESIDENTIAL. REVISE FLOOR PLAN AS
 REQUIRED.
  
 6- A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED
 BY DCA RULE 9N-3 FOR ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS/DETAILS. PROVIDE ONLY THE COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 B) CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR WINDOW
 MULLIONS. PLANS DON'T SHOW ANY WINDOW MULLION. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- BEDROOM EGRESS WINDOW (3-4 SH) SHOWN ON UNIT #1
 DOESN'T COMPLY WITH SEC. R310 OF 2010 FBC-RESIDENTIAL.
 REVISE AS REQUIRED.
  
 8- PROVIDE STRUCTURAL BUCK DETAILS FOR DOORS AND
 WINDOWS. ALSO, COORDINATE WITH PRODUCT APPROVALS
 SUBMITTED. SEE SEC. R612.10 OF 2010 FBC-RESIDENTIAL.
  
 9- NEED TO PROVIDE HEATING AS REQUIRED BY SEC. R303.8
 OF 2010 FBC-RESIDENTIAL. PROVIDE INFORMATION ON PLANS.
 PORTABLE DEVICES ARE NOT ALLOWED.
  
 10- THERE ARE TWO DIFFERENT WALL LEGENDS ON SAME
 DRAWING SHEET 1. WALL LEGEND AND FLOOR PLAN DON'T
 MATCH. REVISE AS REQUIRED AND COORDINATE WITH ITEM #4
 ABOVE. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 11- BATHROOM DOOR ON UNIT #2 DOESN'T COMPLY WITH THE
 29" CLEAR OPENING REQUIRED BY SEC. R320 OF 2010
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712