| 2013-05-30 15:16:45 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | |
| | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | 4. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 5. "SCOPE OF WORK" REFERS TO FRAMING, ENLARGING |
| | OPENINGS, BUT NOTHING SHOWN ON THE PLAN. SEE FBC 107 |
| | REGARDING MINIMUM PLAN REVIEW CRITERIA. PROVIDE |
| | LOCATION AND SCOPE (DETAIL MAY BE REQUIRED). |
| | |
| | 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC |
| | 109. VALUE IS TO INCLUDE ALL LABOR AND MATERIALS, |
| | INCLUDING MATERIALS SUPPLIED BY OTHERS. |
| | |
| | 7. ON THE STOREFRONT PRODUCT APPROVAL, INDICATE OPTIONS |
| | PROPOSED TO SHOW COMPLIANCE WITH WIND DESIGN PRESSURE |
| | REQUIRMENTS FBC 1609. |
| | |
| | |
| | |
| | |