Plan Review Notes
Plan Review Notes For Permit 13050983
Permit Number 13050983
Review Stop B
Sequence Number 1
Notes
Date Text
2013-05-30 15:16:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 5. "SCOPE OF WORK" REFERS TO FRAMING, ENLARGING
 OPENINGS, BUT NOTHING SHOWN ON THE PLAN. SEE FBC 107
 REGARDING MINIMUM PLAN REVIEW CRITERIA. PROVIDE
 LOCATION AND SCOPE (DETAIL MAY BE REQUIRED).
  
 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. VALUE IS TO INCLUDE ALL LABOR AND MATERIALS,
 INCLUDING MATERIALS SUPPLIED BY OTHERS.
  
 7. ON THE STOREFRONT PRODUCT APPROVAL, INDICATE OPTIONS
 PROPOSED TO SHOW COMPLIANCE WITH WIND DESIGN PRESSURE
 REQUIRMENTS FBC 1609.
  
  
  
  