Plan Review Notes
Plan Review Notes For Permit 13050982
Permit Number 13050982
Review Stop B
Sequence Number 4
Notes
Date Text
2013-07-10 16:58:38****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PREVIOUS LISTS NOT FULLY ADDRESSED:
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. IF
 NON COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 TO REPHRASE IN CASE THE FIRST COMMENT WAS NOT CLEAR -
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER.
  
 3RD REVIEW - A LETYTER FROM THE MANUFACTURER WAS
 PROVIDED BUT FLOOR PLAN NOT REVISED WITH REQUESTED
 INFORMATION.
  
  
  