Plan Review Notes
Plan Review Notes For Permit 13050982
Permit Number 13050982
Review Stop B
Sequence Number 3
Notes
Date Text
2013-06-25 09:59:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PREVIOUS LISTS NOT FULLY ADDRESSED:
  
 1. REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 CONTRACTOR HAS STATED THAT EXISTING CLEAR OPENING IS
 29.5", PROPOSED IS 29.5". SINGLE HUNG IN A 50" HIGH
 OPENING CANNOT PROVIDE A CLEAR OPENING WHICH IS GREATER
 THAN HALF OF THE WINDOW SIZE. PLEASE EXPLAIN.
  
 2. REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER.
  
 THIS IS STATED AS 29.5". PROVIDE DOCUMENTATION FROM THE
 MANUFACTURER TO SHOW THAT A 50 5/8" HIGH SINGLE HUNG
 WINDOW WILL PROVIDE AN EGRESS CLEAR OPENING OF 29.5".
 IF THIS IS PROVIDED, DISREGARD ITEM 1.
  