| Plan Review Notes For Permit 13050982 |
| Permit Number |
13050982 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-06-25 09:59:50 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | COMMENT FROM PREVIOUS LISTS NOT FULLY ADDRESSED: | | | | | | 1. REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING | | | DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH | | | EXISTS WHEN THE WINDOW IS FULLY OPEN. | | | | | | CONTRACTOR HAS STATED THAT EXISTING CLEAR OPENING IS | | | 29.5", PROPOSED IS 29.5". SINGLE HUNG IN A 50" HIGH | | | OPENING CANNOT PROVIDE A CLEAR OPENING WHICH IS GREATER | | | THAN HALF OF THE WINDOW SIZE. PLEASE EXPLAIN. | | | | | | 2. REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING | | | DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE | | | MANUFACTURER. | | | | | | THIS IS STATED AS 29.5". PROVIDE DOCUMENTATION FROM THE | | | MANUFACTURER TO SHOW THAT A 50 5/8" HIGH SINGLE HUNG | | | WINDOW WILL PROVIDE AN EGRESS CLEAR OPENING OF 29.5". | | | IF THIS IS PROVIDED, DISREGARD ITEM 1. | | | |
|