Date Text
2013-07-08 11:44:11MORSE GERIATRIC CENTER
 4847 FRED GLADSTONE DRIVE
 MASTER PERMIT # 13050981
 REVISION TRACKING # 13061087
 FIRE ALARM SYSTEM REVISION
  
 1. THE FIRE ALARM SYSTEM INSTALLATION TO COMPLY WITH
 NFPA 72, THE NATIONAL FIRE ALARM CODE.
  
 2. ELECTRICAL SYSTEM INSTALLATION TO COMPLY WITH NFPA
 70, THE NATIONAL ELECTRICAL CODE.
  
 3. THE ENTIRE FIRE ALARM SYSTEM INSTALLATION WHEN
 COMPLETED SHALL BE INSPECTED, TESTED, AND APPROVED BY
 THE FIRE PREVENTION BUREAU.
  
 4. ALL EQUIPMENT USED IN THE INSTALLATION IS TO COMPLY
 WITH THE NATIONAL FIRE ALARM CODE AND SHALL BE APPROVED
 FOR USE IN FIRE ALARM SYSTEMS.
  
 5. AUDIBILITY REQUIREMENTS SHALL BE MET TO ALERT
 PERSONS OF A POSSIBILITY OF A SMOKE OR FIRE EMERGENCY.
  
 6. THE FOLLOWING FOUR SIGNALS SHALL BE REPORTED TO THE
 CENTRAL STATION; WATERFLOW, GENERAL ALARM, SUPERVISORY,
 AND TROUBLE.
  
 7. ACTIVATION OF THE DUCT SMOKE DETETECTORS SHALL CAUSE
 THE AIR HANDLING DEVICE TO SHUT DOWN AND ACTIVATE A
 GENERAL FIRE ALARM SIGNAL.
  
 APPROVED PROVISO
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE