| Plan Review Notes For Permit 13050981 |
| Permit Number |
13050981 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-07-08 11:44:11 | MORSE GERIATRIC CENTER | | | 4847 FRED GLADSTONE DRIVE | | | MASTER PERMIT # 13050981 | | | REVISION TRACKING # 13061087 | | | FIRE ALARM SYSTEM REVISION | | | | | | 1. THE FIRE ALARM SYSTEM INSTALLATION TO COMPLY WITH | | | NFPA 72, THE NATIONAL FIRE ALARM CODE. | | | | | | 2. ELECTRICAL SYSTEM INSTALLATION TO COMPLY WITH NFPA | | | 70, THE NATIONAL ELECTRICAL CODE. | | | | | | 3. THE ENTIRE FIRE ALARM SYSTEM INSTALLATION WHEN | | | COMPLETED SHALL BE INSPECTED, TESTED, AND APPROVED BY | | | THE FIRE PREVENTION BUREAU. | | | | | | 4. ALL EQUIPMENT USED IN THE INSTALLATION IS TO COMPLY | | | WITH THE NATIONAL FIRE ALARM CODE AND SHALL BE APPROVED | | | FOR USE IN FIRE ALARM SYSTEMS. | | | | | | 5. AUDIBILITY REQUIREMENTS SHALL BE MET TO ALERT | | | PERSONS OF A POSSIBILITY OF A SMOKE OR FIRE EMERGENCY. | | | | | | 6. THE FOLLOWING FOUR SIGNALS SHALL BE REPORTED TO THE | | | CENTRAL STATION; WATERFLOW, GENERAL ALARM, SUPERVISORY, | | | AND TROUBLE. | | | | | | 7. ACTIVATION OF THE DUCT SMOKE DETETECTORS SHALL CAUSE | | | THE AIR HANDLING DEVICE TO SHUT DOWN AND ACTIVATE A | | | GENERAL FIRE ALARM SIGNAL. | | | | | | APPROVED PROVISO | | | | | | | | | MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF | | | WEST PALM BEACH FIRE RESCUE |
|