| Plan Review Notes For Permit 13050925 |
| Permit Number |
13050925 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-06-04 17:15:54 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE RAS 117 CALCULATIONS ARE INCORRECT. THIS SINGLE | | | PLY PVC PRODUCT IS MECHANICALLY ATTACHED TO THE ROOF | | | DECK AT THE 3" TABS THAT ARE FABRICATED INTO THE SHEETS | | | BY THE MANUFACTURER. THE TAB SPACING CAN BE DECREASED | | | BY THE MANUFACTURER TO PROVIDE FOR THE HIGHER UPLIFT | | | PRESSURES AT THE CORNER AND PERIMETER AREAS. PLEASE | | | CONTACT DURO-LAST ENGINEERING SERVICES AT 800-248-0280. | | | CITY AMENDMENTS 107.2.1 | | | | | | 2) THE MANUFACTURER'S SPECIFICATIONS STATE THAT THE | | | WIDTH OF THE PERIMETER ROOF AREA MUST NEVER BE LESS | | | THAN 5 FEET. THE RAS 117 CALCULATIONS SPECIFY 3 FEET. | | | PLEASE REVISE. CITY AMENDMENTS 107.2.1 | | | | | | 3) SUBMIT TWO COPIES OF THE MIAMI-DADE OR FLORIDA | | | PRODUCT APPROVALS FOR THE 1/4" DENSDECK INSULATION AND | | | FASTENING REQUIREMENTS. DCA RULE 9N-3 & FBC 1609.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|