2013-05-29 16:35:592010 FBC
  
 DENIED BY BUILDING
  
 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED SPECIFY
 FASTENER SPACING OF 3" OC IN THE CORNER AREAS. SECTION
 8.1 OF RAS 117 STATES THAT THE MINIMUM FASTENER
 SEPARATION SHALL NOT BE LESS THAN 4" OC. PLEASE REVISE.
 CITY AMENDMENTS 107.2.1
  
 2) THE PERMIT APPLICATION SUMMARY FORM AND THE PRODUCT
 APPROVAL LIST 1/4" DENSDECK. PAGE 3 OF THE RAS 117
 CALCULATIONS SPECIFIES 1/2" DENSDECK. PLEASE CLARIFY.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]