| Plan Review Notes For Permit 13050925 |
| Permit Number |
13050925 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-29 16:35:59 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED SPECIFY | | | FASTENER SPACING OF 3" OC IN THE CORNER AREAS. SECTION | | | 8.1 OF RAS 117 STATES THAT THE MINIMUM FASTENER | | | SEPARATION SHALL NOT BE LESS THAN 4" OC. PLEASE REVISE. | | | CITY AMENDMENTS 107.2.1 | | | | | | 2) THE PERMIT APPLICATION SUMMARY FORM AND THE PRODUCT | | | APPROVAL LIST 1/4" DENSDECK. PAGE 3 OF THE RAS 117 | | | CALCULATIONS SPECIFIES 1/2" DENSDECK. PLEASE CLARIFY. | | | CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|