 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 SHEET FP-1 "FIRE PROTECTION NOTE #5": RETAIL SHOULD BE
 DESIGNED TO ORDINARY HAZARD GROUP 2 @ 0.20 GPM/SQ.FT.
 DENSITY TO THE MATCH THE HYDRAULIC CALCULATIONS.
  