Plan Review Notes
Plan Review Notes For Permit 13050866
Permit Number 13050866
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-06-15 09:26:461220 ORTEGA ROAD
 PERMIT #13050866
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 LOADING DOCK INDOOR STORAGE AREA APPEARS TO ONLY HAVE
 ONE EXIT (SIDE SWINGING DOOR). NFPA 101 CHAPTER 40
 (STORAGE OCCUPANCIES) PERMITS A SINGLE MEANS OF EGRESS
 WHEN THE STORAGE HAZARD IS "LOW." HOWEVER, MOST STORAGE
 OCCUPANCIES ARE DEEMED TO BE ORDINARY HAZARD IF ANY
 COMBUSTIBLES ARE PRESENT. IN ORDER TO CLASSIFY AS LOW
 HAZARD, BOTH THE COMMODITY AND THE STORAGE METHOD
 (METAL RACKS, PILED, ETC.) WOULD HAVE TO BE
 NONCOMBUSTIBLE. ANY PALLETIZED, BOXED, ENCAPSULATED
 STORAGE WOULD BE CLASSIFIED AS ORDINARY HAZARD. SITE
 PLAN SHEET INDICATES LOW HAZARD STORAGE. PLEASE
 INDICATE WHAT COMMODITIES WILL BE STORED AND HOW THEY
 WILL BE STORED TO JUSTIFY THE LOW HAZARD
 CLASSIFICATION; OTHERWISE A SECOND SWINGING EXIT DOOR
 WILL BE REQUIRED IF THE COMMON PATH OF TRAVEL EXCEEDS
 50 FEET.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NEW 3068 DOOR SWINGS OVER THE STAIR TREAD.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES. PROVIDE DETAIL.
  
 STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER. PROVIDE DETAIL.
  
 PROVIDE RAMP DETAIL INDICATING ANY HANDRAILS,
 GUARDRAILS OR CURBS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE