Plan Review Notes
Plan Review Notes For Permit 13050866
Permit Number 13050866
Review Stop B
Sequence Number 1
Notes
Date Text
2013-06-10 10:38:03BUILDING PLAN REVIEW
 PERMIT: 13050866
 ADD: 1220 ORTEGA RD
 CONT: WILBUR HOBGOOD CONST.
 TEL: (561)691-9686
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 6/10/2013
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) SHEET A-5:
 2A) 2010 FBC-B 1008.1.6 OR 1009.5 STAIRWAY LANDINGS.
 THE NEW DOORWAY SWINGS OUT OVER THE LANDING.
  
 2B) THE NEW ACCESS RAMP AND DOORWAY THE TOP LANDING
 FROM THE LATCH SIDE OF THE DOOR TO THE EDGE OF THE TOP
 LANDING IS INDICATED AS 1'-4" PLEASE SEE FIGURE
 404.2.4.1(I) FOR DOOR WITH SIDE APPROACH, DOOR PROVIDED
 WITH DOOR CLOSER.
  
 2C) TOP LANDING WILL NEED TO BE A MINIMUM OF 5'0" WIDE
 SINCE THERE IS A 90 DEGREE TURN REQUIRED TO ENTER THE
 NEW ADDITION.
  
 2D) THE PLANS DO NOT PROVIDE ANY STRUCTURAL DETAILS
 (FOUNDATION OR REINFORCING, SLAB) FOR THE NEW
 ACCESSIBLE RAMP NOR THE NEW STAIR LEADING INTO THE NEW
 OFFICE. 2010 WPB ADMINISTRATIVE CODE
 COMMERCIAL PLAN REVIEW: STRUCTURAL REQUIREMENTS,
 ACCESSIBLITY REQUIREMENTS. 2010 FBC-ACCESSIBILITY
 405.1-9.
  
 2E) PLEASE PROVIDE A DETAIL WITH DIMENSIONING, IT
 APPEARS THE WATER CLOSET IS LOCATED 2'-0" CENTERED FROM
 THE WALL, AND THERE IS ONLY 4'-3" FROM THE WALL TO THE
 LAVATORY. 2010 FBC- ACCESSIBILITY CODE 604.2 & 604.3.1
 & FIGURE 604.3.1.
  
 2F) ATTIC STORAGE ABOVE, AND SHEET A-8 TRUSS LOADING NO
 LOADING CRITERIA FOR ATTIC STORAGE PLEASE REVIEW 2010
 FBC-B TABLE 1607.1 (29) ROOFS- ALL OTHER OCCUPANCIES
 300 PSF OR (36) LIGHT 125 PSF.
  
 3) SHEET A-8:
 3A) THIS SHEET LIST THE WIND EXPOSURE AS "B" PLEASE
 CORRECT TO "C" EXPOSURE. 2010 FBC-B 1609.4.2 SURFACE
 ROUGHNESS C THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET IN
 THE UPWIND DIRECTION... TO THE EAST EXPOSURE "C". THIS
 WILL CREATE HIGHER PRESSURES WITH THE EXPOSURE & HEIGHT
 FACTORS.
  
 3B) TYPICAL WALL SECTION, THE LEDGER FOR THE 2 X 12S'
 DOES NOT INDICATE TYPE OR SIZE OF ANCHOR OR IF THERE IS
 A BEAM THAT IT IS BEING ATTACHED TO? THE SAME PROBLEM
 WITH THE ROOF LEDGER NO INFORMATION AS TO WHAT THE
 LEDGERS ARE ATTACHING TO? ADDITIONAL INFORMATION
 REQUIRED, PART OF THE MWFRS.
  
 3C) ADDITIONAL INFORMATION REQUIRED A8 VERSES A6, THE
 PLANS DO NOT PROVIDE EITHER AN INTERMEDIATE TIE BEAM OR
 LINTEL.
 4 DOORS ARE DRAWN TO A 7'-0" ELEVATION
 1 DOOR IS INDICATED TO BE AT ELEVATION 10'-0" TOP OF
 BEAM
 ROOF ELEVATION IS INDICATED AT 12'-0" TOP OF BEAM OR
 12'-9" APPPROX.
 SECTION THROUGH ROOF A-8 MIN ABOVE 14'-0" ABOVE
 LANDING.
  
 4) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. INSULATED ROLL UP-DOORS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 7) SHEET SHEET M-1 INDICATE THE USE OF ROOF STANDS, M2
 INDICATES THE ROOF STANDS BEING TIED DOWN TO A CONCRETE
 DECK PLEASE PROVIDE LOCATION OR ARE THEY BEING PLACED
 ON THE NEW WOOD DECKS? ADDITIONAL INFORMATION REQUIRED.
 107.2.1.3.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved