Plan Review Notes
Plan Review Notes For Permit 13050856
Permit Number 13050856
Review Stop P
Sequence Number 2
Notes
Date Text
2013-06-24 10:21:462010 FBC
  
 DENIED BY PLUMBING
  
 1) THE PENTAIR WHISPERFLO 1HP, 2-SPEED POOL PUMP
 (WFE-24) HAS A FLOW RATE OF APPROXIMATELY 110 GPM WITH
 A TDH OF 30 FT. ON HIGH SPEED. THE WATER VELOCITY IN
 THE 2" PIPE THAT IS SPECIFIED IS 11.25 FT/SEC AT THAT
 RATE. THIS EXCEEDS THE MAXIMUM WATER VELOCITY ALLOWED
 IN FIELD FABRICATED BRANCH SUCTION PIPING WHICH IS 6
 FEET PER SECOND WHEN ONE OF A PAIR IS BLOCKED AND THE 8
 FEET/SEC FOR SUCTION PIPING. PLEASE CORRECT. FBC
 R4101.6.3 AND ANSI / APSP-7 2006 SECTION 4.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]