| Plan Review Notes For Permit 13050856 |
| Permit Number |
13050856 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-06-24 10:21:46 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) THE PENTAIR WHISPERFLO 1HP, 2-SPEED POOL PUMP | | | (WFE-24) HAS A FLOW RATE OF APPROXIMATELY 110 GPM WITH | | | A TDH OF 30 FT. ON HIGH SPEED. THE WATER VELOCITY IN | | | THE 2" PIPE THAT IS SPECIFIED IS 11.25 FT/SEC AT THAT | | | RATE. THIS EXCEEDS THE MAXIMUM WATER VELOCITY ALLOWED | | | IN FIELD FABRICATED BRANCH SUCTION PIPING WHICH IS 6 | | | FEET PER SECOND WHEN ONE OF A PAIR IS BLOCKED AND THE 8 | | | FEET/SEC FOR SUCTION PIPING. PLEASE CORRECT. FBC | | | R4101.6.3 AND ANSI / APSP-7 2006 SECTION 4.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|