| Plan Review Notes For Permit 13050856 |
| Permit Number |
13050856 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-12 13:54:15 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) THE ATMOSPHERIC VENT ARRANGEMENT IS NO LONGER AN | | | ACCEPTABLE METHOD OF ENTRAPMENT PROTECTION FOR NEW | | | POOLS. SEE ANSI/APSP-7 2006 SECTION 7. | | | | | | 2) PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATIONS | | | WITH THE PUMP CURVE FOR THE 3/4 HP POOL PUMP IN ORDER | | | TO VERIFY THE WATER VELOCITY IN THE POOL PIPING. THE | | | WATER VELOCITY IN FIELD FABRICATED BRANCH SUCTION | | | PIPING IS 6 FEET PER SECOND WHEN ONE OF A PAIR IS | | | BLOCKED. ANSI / APSP-7 2006 SECTION 4.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|