2013-06-12 13:54:152010 FBC
  
 DENIED BY PLUMBING
  
 1) THE ATMOSPHERIC VENT ARRANGEMENT IS NO LONGER AN
 ACCEPTABLE METHOD OF ENTRAPMENT PROTECTION FOR NEW
 POOLS. SEE ANSI/APSP-7 2006 SECTION 7.
  
 2) PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATIONS
 WITH THE PUMP CURVE FOR THE 3/4 HP POOL PUMP IN ORDER
 TO VERIFY THE WATER VELOCITY IN THE POOL PIPING. THE
 WATER VELOCITY IN FIELD FABRICATED BRANCH SUCTION
 PIPING IS 6 FEET PER SECOND WHEN ONE OF A PAIR IS
 BLOCKED. ANSI / APSP-7 2006 SECTION 4.4
  