| Date |
Text |
| 2013-06-13 13:09:30 | 525 OKEECHOBEE BLVD, SUITE 860 |
| | PERMIT # 13050829 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****PROVISO***** |
| | |
| | COVER SHEET - UPDATE THE CODE LIST TO REFERENCE THE |
| | 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS |
| | |
| | COVER SHEET - "FIRE PROTECTION SYSTEMS SHALL REMAIN |
| | ACTIVE DURING DEMOLITION AND RENOVATION ACTIVITIES. IN |
| | THE EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE |
| | FOR MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected]) OR |
| | IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE |
| | OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE |
| | HIGHWAY." |
| | |
| | SHEET A-1.0 - THE TENANT SPACE IS FUNCTIONING AS A |
| | MULTIUSE OCCUPANCY - BUSINESS AND ASSEMBLY. FOR |
| | NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST STRINGENT |
| | FIRE AND LIFE SAFETY REQUIREMENTS OF EACH OCCUPANCY |
| | SHALL APPLY TO THE BUILDING. PER FBC SECTION 508.2 |
| | AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE |
| | THAN TEN PERCENT IN WHICH THEY ARE LOCATED. |
| | |
| | PER SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN |
| | OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE |
| | OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY. |
| | |
| | SHEET A -1.0 - FOR DOOR #820 OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE |
| | SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. |
| | NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT |
| | BE RELEASED BY THE PANIC HARDWARE. |
| | |
| | SHEET E -1.0 PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED |
| | EGRESS DOORS ARE PERMITTED PROVIDED THAT ALL SEVEN OF |
| | THE FOLLOWING CRITERIA ARE MET: |
| | 1.A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| | ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT |
| | ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON |
| | DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER |
| | TO THE SENSOR. |
| | 2.LOSS OF POWER TO THE PART OF THE ACCESS CONTROL |
| | SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| | THE DOORS IN THE DIRECTION OF EGRESS. |
| | 3.THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE |
| | DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| | LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND |
| | WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS. |
| | 4.THE MANUAL RELEASE DEVICE SHALL BE READILY ACCESSIBLE |
| | AND CLEARLY IDENTIFIED BY A SIGN THAT READS PUSH TO |
| | EXIT. |
| | 5.WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL RESULT |
| | IN DIRECT INTERRUPTION OF POWER TO THE LOCK, |
| | INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS, |
| | AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| | 30 SECONDS. |
| | 6.ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | 7.ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER SYSTEM |
| | OR AUTOMATIC DETECTION SYSTEM SHALL AUTOMATICALLY |
| | UNLOCK THE DOORS IN THE DIRECTION OF EGRESS, AND THE |
| | DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM |
| | HAS BEEN MANUALLY RESET. |
| | |
| | LAUREN PHILMORE |
| | FIRE INSPECTOR II / INVESTIGATOR I |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 804-4783 |
| | |
| | |