| 2013-05-24 08:44:02 | 2010 FBC AND 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) THE ELECTRICAL DIAGRAM ON SHEET 2 SPECIFIES A GAS | | | HEATER AND SHEET 1, THE CUT SHEETS AND LOAD | | | CALCULATIONS ARE FOR AN ELECTRIC HEAT PUMP. PLEASE | | | REVISE SHEET 2 TO SHOW THE CORRECT PANEL AND WIRE SIZES | | | FOR THE 6.9 KW HEAT PUMP. CITY AMENDMENTS 107.2.1 NEC | | | 215, 220, 240.4 & 310.15 | | | | | | 2) AT LEAST ONE 15 OR 20 AMP GFCI RECEPTACLE LOCATED | | | BETWEEN 6 AND 20 FEET OF THE POOL IS REQUIRED BY NEC | | | 680.22(A)(3). | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|