2013-06-10 09:34:44RESIDENTIAL (R3) ADDITION/ALTERATION PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM:
 A) MISSING MASTER BATHROOM WATER CLOSET AND WASHER.
 ALSO, MISSING KITCHEN DOUBLE SINK. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 B) PROVIDE CLEAR PLUMBING RISER DIAGRAM THAT MATCHES
 FLOOR PLAN. IDENTIFY EACH FIXTURE LOCATION. FOR EXAMPLE
 MASTER BATHROOM, BUTLERS PANTRY, BATHROOM #2, ETC. THIS
 WILL FACILITATE THE REVIEW PROCESS AND HELP AVOID
 CONFUSION. SEC. 107.2.1
  
 C) VENTING SHOWN ON THE PLUMBING RISER DIAGRAM IS NOT
 LEGIBLE AND IS INCOMPLETE. SOME VENTS ARE SHOWN CUT AND
 LEADING TO NOWHERE. SEC. 107.2.1.
  
 D) REVISE VENTS TO COMPLY WITH SEC. 3108 OF 2010
 FBC-RESIDENTIAL. ONLY THE BATHROOM GROUP IS ALLOWED TO
 BE WET VENTED. AND ALL THE FIXTURES NEED TO BE PROPERLY
 VENTED. NO MORE THAN ONE WET VENTED FIXTURE SHALL
 DISCHARGE UPSTREAM OF THE DRY VENTED FIXTURE DRAIN
 CONNECTION.
  
 F) THE LAVATORIES SHOWN FOR GUEST BATH ARE INCORRECT.
 THERE ARE TWO INDEPENDENT LAVATORIES NO DOUBLE
 LAVATORY. SEC. 107.2.1
  
  
  