| Notes |
| Date |
Text |
| 2013-05-31 09:27:00 | 5-31-13 - FIRST REVIEW | | | 1. NEC 408.4 - REVISE PANEL SCHEDULE TO COMPLY WITH | | | THIS SECTION. CIRCUITS SHOULD SHOW CLEAR EVIDENT AND | | | SPECIFIC PURPOSE FOR USE. "GENERAL LIGHTING" NOT | | | ACCEPTABLE PER CODE | | | 2. AFCI RECEPTACLES NOT FOR SLEEPING AREAS ONLY. | | | PROVIDE FOR ALL REQUIRED RECEPTS PER NEC 210.12B | | | 3. PROVIDE TAMPER RESISTANT RECEPTACLES FOR ALL | | | REQUIRED RECEPTCELS PER NEC 406.11 AND 210.52 | | | VB |
|