| Plan Review Notes For Permit 13050784 |
| Permit Number |
13050784 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-04 10:24:59 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. | | | 233-5025 FOR MORE INFORMATION. PRIOR TO PERMIT | | | ISSUANCE,THE PLANS ARE TO BE STAMPED AND THE RECEIPT | | | FOR PAYMENT PROVIDED. | | | | | | 2. VALUE TOO LOW. VALUE TO INCLUDE ALL MATERIALS AND | | | LABOR, FBC 109. PROVIDE A COPY OF THE CONTRACT FOR THIS | | | JOB. A COST BREAKDOWN MAY BE REQUIRED. | | | | | | 3. THIS PARCEL IS LOCATED IN FLOOD ZONE A5, 7.0 BFE. | | | PROVIDE AN ELEVATION CERTIFICATE, "CONSTRUCTION | | | DRAWINGS." TWO ADDITIONAL ELEVATION CERTIFICATES WILL | | | BE REQUIRED, "BUILDING UNDER CONSTRUCTION" AND | | | "FINISHED CONSTRUCTION." | | | | | | 4. SP 1 STATES THIS IS TYPE II CONSTRUCTION, PLEASE | | | REVISE, SEE FBC CHAPTER 6. TYPE II IS NON COMBUSTIBLE | | | CONSTRUCTION. | | | | | | 5. PROVIDE A SOILS INVESTIGATION REPORT. PRIOR TO | | | RESUBMITTAL, DESIGNER TO REVIEW REPORT FINDINGS AND | | | REVISE FOUNDATION DESIGN IF REQUIRED. | | | | | | 6. SEE FBC 2010 ENERGY CONSERVATION 402.5, SHGC NOT TO | | | EXCEED .50. ENERGY CALCS SHOW SHGC OF .66 AND "CLEAR, | | | DEFAULT." PLEASE REVISE. | | | | | | | | | |
|