| 2013-06-05 10:22:55 | 6-5-13 | | | FIRST REVIEW | | | 1. COMMERCIAL EQUIPMENT LIKELY TO BE SERVICE WHILE | | | ENERGIZED MUST HAVE SAFETY WARNING LABEL TO PROTECT | | | FROM ARC FLASH HAZARD PER NES 110.16 | | | 2. CONFERENCE ROOM FLOOR BOX CONDUCTORS MUST BE RATED | | | FOR WETLOCATION PER NEC 300.5B | | | 3. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS CU'S TO | | | HAVE MOCP OF 30/2. PANEL A SHOWS 50/2 AND PANEL B SHOWS | | | 4-/2. PLEASE REVISE | | | 4. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS AHU#2 TO | | | HAVE MOCP OF 40/2. PANEL B SHOWS 50/2. PLEASE REVISE. | | | VB |
|