| Plan Review Notes For Permit 13050773 |
| Permit Number |
13050773 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-02 13:41:29 | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | SHEET MP-1: PLEASE REVISE THE PLUMBING ISO TO REMOVE | | | THE HORIZONTAL DRY VENTS ON THE SECOND FLOOR WATER | | | CLOSET & BETWEEN THE TUB AND SHOWER. | | | P3104.3 VENT CONNECTION TO DRAINAGE SYSTEM. | | | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL | | | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN | | | PIPE. | | | P3104.4 VERTICAL RISE OF VENT. | | | EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 | | | INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE | | | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|