2013-07-02 13:34:34FBC 2010 FUEL GAS REVIEW #1
 DENIED:
  
 1. NO FUEL GAS INFORMATION OR DRAWINGS WERE INCLUDED
 WITH THE PLANS.
  
 2. THE DRYERS ARE SHOWN IN A CLOSET THAT IS USED FOR
 OTHER PURPOSES.
 G2406.2 (303.3) PROHIBITED LOCATIONS.
 APPLIANCES SHALL NOT BE LOCATED IN SLEEPING ROOMS,
 BATHROOMS, TOILET ROOMS, STORAGE CLOSETS OR SURGICAL
 ROOMS, OR IN A SPACE THAT OPENS ONLY INTO SUCH ROOMS OR
 SPACES, EXCEPT WHERE THE INSTALLATION COMPLIES WITH ONE
 OF THE FOLLOWING:
 5. THE APPLIANCE IS INSTALLED IN A ROOM OR SPACE THAT
 OPENS ONLY INTO A BEDROOM OR BATHROOM, AND SUCH ROOM OR
 SPACE IS USED FOR NO OTHER PURPOSE AND IS PROVIDED WITH
 A SOLID WEATHER-STRIPPED DOOR EQUIPPED WITH AN APPROVED
 SELF-CLOSING DEVICE. ALL COMBUSTION AIR SHALL BE TAKEN
 DIRECTLY FROM THE OUTDOORS IN ACCORDANCE WITH SECTION
 G2407.6.
  