| Plan Review Notes For Permit 13050773 |
| Permit Number |
13050773 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-07 10:21:09 | 6-7-13 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS OR | | | CLARIFICATIONS; | | | 1. CHANGE NOTE #19 FROM "SLEEPING AREAS" TO ALL | | | REQUIRED AREAS PER NEC 210.12B | | | 2. ADD SMOKE DETECTORS IN NEW ADDITION PER FBC (TOP AND | | | BOTTOM OF STAIRS) AND IN THE EXISTING HOME IF NOT | | | ALREADY THERE. (SEE RESIDENTIAL CODE SECTION 314 & 315) | | | MUST USE CARBON MONOXIDE DETECTORS WITHIN 10 FEET OF | | | SLEEPING AREAS. | | | 3. NEC 230.2 STATES ONE ONE SERVICE PER BUILDING. IT | | | SEEMS THERE ARE GOING TO BE 2 METERS. ONE IS EXISTING | | | TO REMAIN AND ONE NEW. PLEASE CLARIFY. | | | VB |
|