| Date |
Text |
| 2013-07-02 10:07:07 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY BUILDING (2300 N. JOG RD) TO VERIFY IF IMPACT |
| | FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY |
| | OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- SHEET A-1. REVISE THE DESIGN WIND LOADS: |
| | A) WINDOWS AND DOORS DESIGN PRESSURES DON'T CORRESPOND |
| | TO EXPOSURE "D" AND TO WORST CASE SCENARIO. PROVIDE |
| | CALCULATIONS. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. |
| | |
| | B) REVISE ROOF DESIGN LOADS. PROVIDE CALCULATIONS. SEC. |
| | 107.2.1.3 CITY AMENDMENTS. (1) DESIGN PRESSURES SHOWN |
| | DON'T CORRESPOND TO EXPOSURE "D". (2) CLARIFY WHY THE |
| | DESIGN PRESSURES FOR ZONE 2 AND ZONE ARE THE SAME. (3) |
| | REVISE THE DIMENSION GIVEN FOR THE ROOF ZONE 2 AND 3. |
| | SEE FOOTNOTE "A" ON FIGURE R301.2(7) AND REVISE AS |
| | REQUIRED. |
| | |
| | C) SPECIFY ALL LOADS INCLUDING ATTIC AND BALCONY LIVE |
| | LOADS AS REQUIRED BY TABLE R301.5 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- A) PROVIDE COMPLETE SIGNED AND SEALED ENGINEERED |
| | PACKAGE FOR THE CONSTRUCTION OF THE ICF WALL SYSTEM. |
| | PROVIDE SPECIFICATIONS, DETAILS, SECTIONS, ELEVATIONS, |
| | BEAMS, LINTELS, CANTILEVERED BALCONY CONSTRUCTION, |
| | REINFORCEMENT AT OPENINGS, ETC. SEC. 107.2.1.3 CITY |
| | AMENDMENTS TO FBC. |
| | ***NOTE; COORDINATE WITH THE REVISED DESIGN CRITERIA |
| | SPECIFIED BY THE ARCHITECT OF RECORD ON SHEET A-1. |
| | |
| | B) PROVIDE SPECIFICATIONS FOR THE INSULATION USED IN |
| | THE ICF WALL ASSEMBLY TO SHOW COMPLIANCE WITH SEC. R316 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF COVERING AT NEW BALCONY AREA. ***NOTE: CLEARLY |
| | IDENTIFY THE APPROVED ASSEMBLY TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES REQUIRED BY SEC. |
| | R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. (***NOTE: IF |
| | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES. |
| | THEN SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE |
| | REQUIRED). |
| | |
| | B) ROOF SHINGLES. NOA 11-0411.02 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE |
| | AND DOWNLOAD CURRENT NOA. |
| | |
| | C) ALL SIMPSON AND USP CONNECTORS SPECIFIED ON THE |
| | CONNECTION SCHEDULE ON SHEET S-1 AND IN ALL DETAILS AND |
| | SPECIFICATIONS. ***NOTE: PROVIDE ONLY THE PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR. |
| | |
| | C) EXTERIOR DOORS SHOWN ON ELEVATIONS FOR THE FIRST |
| | FLOOR BATHROOM AND STORAGE. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 6- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS |
| | INCLUDING OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES. SEC. 109.3 OF CITY AMENDMENTS TO |
| | FBC. VALUATION WAS UPDATED TO $174,112. THE PERMIT FEE |
| | BALANCE IS $3926.42. |
| | |
| | 8- SPECIFY CARBON MONOXIDE ALARMS ON PLANS, INCLUDING |
| | THE EXISTING BEDROOMS AS REQUIRED BY SEC. R315 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 9- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THE |
| | STRUCTURAL BUCK DETAIL FOR DOORS AND WINDOWS ON THE |
| | PROPOSED ICF WALL SYSTEM. SEC. 107.2.1.3 OF CITY |
| | AMENDMENTS TO SHOW COMPLIANCE WITH SEC. R301.2.1.4.3 |
| | AND SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 10- SPECIFY SIZE OF ATTIC ACCESS. SEC. R807 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 11- SHEET A-2: |
| | A) STAIR SECTION: REVISE THE HANDRAIL HEIGHT TO COMPLY |
| | WITH SEC. R311.7.7.1. |
| | B) PROVIDE ALL DIMENSIONS ON THE STAIRWAY TO VERIFY |
| | COMPLIANCE WITH SEC. R311.7.1 AND SEC. R311.7.5 OF 2010 |
| | FBC-RESIDENTIAL. |
| | C) SPECIFY FIREBLOCKING IN THE STAIRWAY AS REQUIRED BY |
| | SEC. R302.11 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 12- SHEET S-1: |
| | A) FOUNDATION PLAN: CLARIFY REINFORCEMENT SPECIFIED FOR |
| | THE WALL. SPECIFICATIONS SHOWN ARE FOR AN STANDARD |
| | CONCRETE BLOCK FILLED CELL. COORDINATE WITH ICF WALL |
| | SYSTEM. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | B) PROVIDE DETAIL/SECTION AND SPECIFICATIONS FOR THE |
| | LINTEL SCHEDULE SHOWN. PROVIDE ALL DIMENSIONS AND |
| | COORDINATE WITH ICF WALL SYSTEM. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | C) DETAIL SECTION 1: (1) SPECIFY HOW LONG ARE THE |
| | ANCHORS BOLTS USED TO FASTEN THE 2X8 LEDGER. (2) |
| | COORDINATE ANCHOR TYPE AND SPACING USED TO FASTEN 2X8 |
| | LEDGER WITH ANCHOR SPECIFIED ON WALL SECTIONS ON SHEET |
| | S-2. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | D) WHERE IS SECTION DETAIL 4/S-2 SHOWN ON THE SECOND |
| | FLOOR PLAN BY THE STAIRWAY. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | E) ROOF FRAMING PLAN: REVISE THE ROOF SHEATHING |
| | SPECIFICATIONS. ALL NAILS TO BE 8D RING SHANK AND ROOF |
| | ZONE REQUIRES NAILS AT 4"OO.C. SEC. R803.2.3.1 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | F) REVISE THE PLYWOOD SHEATHING NAILING SCHEDULE TABLE: |
| | (1) SEE COMMENT #12(E) ABOVE. (2) CLARIFY NOTE STATING |
| | THAT RING SHANK NAILS ARE NOT REQUIRED WHEN MEAN ROOF |
| | HEIGHT IS LESS THAN 25'. SPECIFY WHAT SECTION OF THE |
| | CODE STATES THIS STATEMENT. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | G) UPDATE THE BUILDING CODE SPECIFIED ON THE NOTE #1 |
| | SHOWN BELOW THE TYPICAL WOOD BUCK TO CONCRETE |
| | CONNECTION DETAIL HEADING. |
| | |
| | H) TRUSS PACKAGE SPECIFY FLOOR TRUSSES TO BE MAX. 19.4" |
| | O.C. SECOND FLORO PLAN CALLS FOR 24"O.C. COORDINATE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | I) ROOF TRUSSES REQUIRE 8" MIN. BEARING. COORDINATE |
| | WITH TRUSS PACKAGE AND ICF WALL SYSTEM. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 13- SHEET S-2: |
| | A) CLARIFY IF DESIGNING A VENTED OR UNVENTED ATTIC. ALL |
| | WALL SECTIONS SHOW CLOSED CELL INSULATIONS AND BATT |
| | INSULATION. ALSO, WALL SECTIONS SHOW ATTIC VENTILATION |
| | ON THE SOFFIT. REVISE AS REQUIRED. IF USING |
| | VENTILATION, THEN SPECIFY THE VENT SIZE AND LOCATION. |
| | IF USING CLOSED CELL INSULATION, THEN PROVIDE |
| | MANUFACTURER SPECIFICATIONS. COORDINATE WITH THE ENERGY |
| | CALCULATIONS, INCLUDING R-VALUE FOR WALLS AND CEILINGS. |
| | SEC R806 OF 2010 FBC-RESIDENTIAL. |
| | |
| | B) SPECIFY FIREBLOCKING (AT FLOOR ASSEMBLY AND WALL TO |
| | CEILING) IN ALL WALL SECTIONS AS REQUIRED BY SEC. |
| | R302.11 OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) PROVIDE SPECIFICATIONS AND DETAILS ON WALL SECTIONS |
| | SHOWING COMPLIANCE WITH THE TERMITE PROTECTION REQUIRED |
| | BY SEC. R318.5 OF 2010 FBC-RESIDENTIAL. |
| | |
| | D) WALL SECTIONS TO SHOW COMPLIANCE WITH INSPECTION FOR |
| | TERMITES SEC. R704 OF 2010 FBC-RESIDENTIAL. |
| | |
| | E) FOOTING NEEDS TO BE 12" BELOW GRADE. SEC. R403.1.4 |
| | OF 2010 FBC-RESIDENTIAL. NEED TO REVISE FOOTING SIZE ON |
| | SHEET S-1 AND WALL SECTIONS ACCORDINGLY. |
| | |
| | F) ALL WALL SECTIONS: SPECIFY HOW LONG ARE THE ANCHORS |
| | USED TO SUPPORT THE WOOD LEDGERS THAT SUPPORT HE FLOOR |
| | TRUSSES. COORDINATE ANCHOR WITH SECTION 1 ON S-1. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | G) SECTION -2: CLARIFY SPECIFICATIONS FOR "#5 DOWEL @ |
| | 24"O.C. DRILL & EPOXY - 4" EMBED.". WHERE IS THIS |
| | EMBEDDED INTO?. SPECIFY BEAM SUPPORTING THIS WALL. SEC. |
| | 107.2.1.3 CITY AMENDMENTS. |
| | |
| | H) SPECIFY FIREBLOCKING ON SECTION-F. SEC. R302.11 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | 14- REVISE ENERGY CALCULATIONS: |
| | A) COORDINATE WITH ARCHITECTURAL PLANS. VENTED OR |
| | UNVENTED ATTIC. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | B) COORDINATE R VALUE FOR WALL AND CEILINGS WITH |
| | ARCHITECTURAL PLANS. SEC. 107.2.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | C) THERE ARE NO WOOD DOORS SHOWN ON PLANS AND PRODUCT |
| | APPROVALS. REVISE PAGE 3 OF 5. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | D) CLARIFY WHY HEATING SYSTEM, COOLING SYSTEM AND DUCT |
| | SAY "INVALID" ????. SEC. 107.2.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | E) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING THE |
| | BUILDER NAME. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 15- REVISE TRUSS PACKAGE (SEC. 61G15-31.003): |
| | A) TRUSSES WERE DESIGNED FOR EXPOSURE "C". ARCHITECT'S |
| | PLANS SPECIFY EXPOSURE "D". REVISE AS REQUIRED. SEC. |
| | R301.2.1.3 OF 2010 FBC-RESIDENTIAL. |
| | |
| | B) COVER SHEET IS MISSING THE NAME OF THE ARCHITECT OF |
| | RECORD. |
| | |
| | C) INDIVIDUAL TRUSSES ARE MISSING THE TITLE BLOCK AND |
| | INFORMATION OF THE TRUSS ENGINEER. |
| | |
| | D) THE CORNER SETS AND PIGGY BACK TRUSSES DETAILS NEED |
| | TO BE UPDATED TO CURRENT CODES. |
| | |
| | E) INDIVIDUAL FLOOR TRUSSES SPECIFY MAXIMUM SPACING AT |
| | 19.4", WHILE TRUSS LAYOUT SPECIFY 24" O.C.. REVISE AS |
| | REQUIRED. |
| | |
| | F) COORDINATE ROOF TRUSSES REQUIRED BEARING AT THE ENDS |
| | (8" SHOWN ON INDIVIDUAL TRUSSES) WITH ICF WALL SYSTEM |
| | SPECIFIED BY THE ARCHITECT OF RECORD. |
| | |
| | G) ARCHITECT OF RECORD TO REVIEW TRUSS PACKAGE BEFORE |
| | SUBMITTAL. |
| | |
| | |
| | ***NOTE: PROVIDE RESPONSE LETTER TO EACH ITEM TO |
| | EXPEDITE THE REVIEW PROCESS AND MAKE SURE EVERY ITEM IS |
| | ADDRESSED. THANK YOU. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |