| 2013-09-18 08:55:15 | BUILDING PLAN REVIEW |
| | PERMIT:13050770 |
| | ADD: MASTER PLAN NEW & MODIFIED TROLLEY SHELTERS |
| | CONT: TBD |
| | CONTACT: VIVEK GALAV |
| | TEL: (561)494-1061 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SEPT 18/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. THE MODIFIED AND NEW TROLLEY SHELTERS |
| | ARE GOING TO BE MASTERED WE WILL NEED THE SHOP DRAWINGS |
| | THAT PROVIDE THE FASTENING DETAILS FOR ALL OF THE |
| | FRAMING MEMBERS. THE 700 SERIES OF SHEETS INDICATE ALL |
| | CONNECTIONS ARE TO BE WELDED OR CONCEALED FASTENERS |
| | SHOP DRAWING ARE TO INCLUDE ALL CONNECTION METHODS FOR |
| | ARCHIETECT REVIEW. 2010 WPB ADMINISTRATIVE CODE, |
| | CHAPTER 1 ADMINISTRATION, 2010 EDITION.107.3.5.1.1(8) |
| | MINIMUM PLAN REVIEW CRITERIA COMMERCIAL BUILDINGS, |
| | STRUCTURAL. |
| | |
| | 2) PROVISO: NOT PART OF THIS PERMIT. SHEET A2.02 ROOF |
| | PLANS FOR NEW AND RENOVATED SHELTERS ALSO INDICATES THE |
| | USE OF SOLAR PHOTOVOLTIAC SYSTEMS, PLEASE NOTE THIS |
| | SYSTEM WILL REQUIRE A SEPERATE ELECTRICAL PERMIT AND |
| | ASSOCIATED FEES. PLEASE BACK OUT THE VALUE FOR THIS |
| | SYSTEM OUT OF THE BUILDING COST TO BE COVERED UNDER THE |
| | PHOTOVOLTIAC ELECTRIC PERMIT. 109.3 WPB ADMINISTRATIVE |
| | CODE, BUILDING PERMIT VALUATION. |
| | |
| | 3) 2ND REQUEST. SHEET A2.02 IN THE ROOFING NOTES |
| | DESCRIBES A ROOFING SYSTEM, KEMPEROL 2K-PUR: FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) (D) ROOFING PRODUCTS AND ASSEMBLIES PLEASE |
| | SUBMIT 2 COPIES OF PRODUCT APPROVAL, PLEASE CIRCLE THE |
| | SYSTEM THAT WILL BE ATTACHED TO ALUMINUM TUBING/ DECK |
| | AS DEPICTED ON A2.02. A ENGINEER MAY DO RATIONAL |
| | ANYLSIS IF THE PRODUCT WAS TESTED ON A STEEL DECK TO |
| | THE ALUMINUM DECK/ TUBING. |
| | |
| | 4) COMPLIED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |