Plan Review Notes
Plan Review Notes For Permit 13050755
Permit Number 13050755
Review Stop E
Sequence Number 1
Notes
Date Text
2013-06-03 16:49:586-3-13
  
 FIRST REVIEW
 1. CHECK NOTE 16.14. CALLS FOR ALL ROMEX WIRING. IS
 THAT CORRECT?
 2. PLEASE COMPLY THE THE FOLLOWING NEC SECTIONS:
 210.12B AFCI PROTECTION; 210.8A GFCI RECEPTS WITHIN 6
 FEET OF SINKS; 210.52 REQUIRED RECEPTS AT KITCHEN
 ISLANDS; 406.11 TAMPER RESISTANT RECEPTS; 408.4 PROVIDE
 PANEL DIRECTORY
 VB