Plan Review Notes
Plan Review Notes For Permit 13050750
Permit Number 13050750
Review Stop E
Sequence Number 1
Notes
Date Text
2013-05-30 10:53:285-30-13 - FIRST REVIEW
  
 PROVIDE ELECTRICAL ONE LINE RISER DIAGRAM PER NEC 215.5
 LIGHT FIXTURES MUST COMPLY WITH NEC 410.130G
 PER NEC 547.10, PROTECTION OF ANIMALS IN CONFINEMENT
 MUST HAVE AN EQUIPOTENTIAL PLANE INSTALLED TO BOND ALL
 EQUIPMENT AND METAL OBJECTS LIKELY TO BECOME ENERGIZED.
 FURTHER REFERNCE FOUND IN AMERICAN SOCIETY OF
 AGRICULTURAL AND BIOLOGICAL ENGINEERS. (ASABE)
 SPECIFICATIONS. (EP473.2-2001 FOR BONDING AND
 EP342.2-1995 FOR WATERERS.)
 PER NEC 682 REQUIREMENTS FOR NATURAL AND ARTIFICIAL
 BODIES OF WATER, CONTROLS AREA MUST HAVE PROPER
 GROUNDING AND BONDING PROTECTION FOR SERVICE PERSONNEL.
 (SECT 682.33 SPECIFICALLY)
 PLEASE PROVIDE DETAIL OF THIS AREA SHOWING ELECTRICAL
 DATA, CIRCUITRY AND BONDING.
 VB