| 2013-06-07 14:24:20 | 504 CLEAR LAKE AVENUE |
| | OCCUPANCY: GROUP DAY-CARE HOME WITH 7 TO 12 CLIENTS |
| | PERMIT #13050746 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN SHALL COMPLY WITH CHAPTER 16 (NEW DAY-CARE |
| | OCCUPANCY) OF THE 2010 EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH |
| | NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT DOORS, |
| | RESCUE WINDOWS, FIRE EXTINGUISHERS, AND LIGHTING. |
| | INDICATE IF THE ENTIRE HOUSE IS BEING USED FOR DAY-CARE |
| | OR JUST THE ONE ROOM. |
| | |
| | SINGLE/MULTI-STATION SMOKE ALARMS OR SMOKE DETECTORS |
| | (HARD-WIRED OR BATTERY POWERED) SHALL BE INSTALLED IN |
| | ALL AREAS USED FOR SLEEPING. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL |
| | AREA. |
| | |
| | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS. |
| | |
| | AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| | BUILDING PRIOR TO OCCUPANCY. |
| | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL |
| | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A |
| | COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN |
| | A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL |
| | BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO |
| | ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED |
| | CLEAR OF OBSTRUCTIONS. |
| | |
| | ESCAPE/RESCUE WINDOWS |
| | (1) SUCH WINDOWS SHALL BE OPERABLE FROM THE INSIDE |
| | WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN 20-INCHES IN WIDTH, 24-INCHES |
| | IN HEIGHT, AND 5.7 SQ.FT. IN AREA. |
| | (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN |
| | 44-INCHES ABOVE THE FLOOR. |
| | (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, |
| | WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE |
| | REQUIRED 5.7 SQ.FT. OPENING AND A DEPTH OF NOT LESS |
| | THAN 20-INCEHS TO PASS FULLY THROUGH THE OPENING. |
| | |
| | AT THIS TIME, A THOROUGH AND COMPLETE PLAN REVIEW |
| | CANNOT BE PERFORMED DUE TO A LACK OF PLAN INFORMATION. |
| | |