2013-05-31 13:48:57BUILDING PLAN REVIEW
 PERMIT: 13050746
 ADD: 504 CLEAR LAKE AVE
 CONT: TBD
 TEL: (561)832-0472 MARY
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/31/2013
 ACTION: DENIED
 NOTE CHANGE OF OCCUPANCY FROM DAY CARE 4 TO 12
 CHILDREN.
  
 2010 WEST PALM BEACH ADMINISTRATIVE CODE 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 1) PLEASE PROVIDE ADDITIONAL INFORMATION, IS THIS
 DAYCARE GOING TO OCCUPY THE WHOLE BUILDING OR IS PART
 OF THIS BUILDING STILL GOING TO REMAIN A R-3 RESIDENCE
 AND BE CONSIDERED A MIXED USE BUILDING? HOW LONG WILL
 THE CHILDREN BE THERE DAILY? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THIS PLAN REVIEW WILL CONSIDER
 THIS USAGE AS A MIXED USE OCCUPANCY. 2010 EXISTING
 BUILDING CODE 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY.
  
 2) THE SUBMITTED PLANS WILL NEED TO DETERMINE IF THE
 DESIGN IS TO BE 912.1.1.1 CHANGE OF OCCUPANCY
 CLASSIFICATION WITHOUT SEPARATION OR 912.1.1.2 CHANGE
 OF OCCUPANCY CLASSIFICATION WITH SEPARATION.
  
 3) 2010 EXISTING BUILDING CODE 912.2.2 FIRE ALARM AND
 DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS THAT REQUIRES A FIRE ALARM AND
 DETECTION SYSTEM TO BE PROVIDED BASED ON THE NEW
 OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS. EXISTING ALARM NOTIFICATION APPLIANCES SHALL BE
 AUTOMATICALLY ACTIVATED THROUGHOUT THE BUILDING. WHERE
 THE BUILDING IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM,
 ALARM NOTIFICATION APPLIANCES SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
 2010 FBC-B 436.7.2 DETECTION. A SMOKE DETECTION SYSTEM
 SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72, WITH
 PLACEMENT OF DETECTORS IN EACH STORY IN FRONT OF DOORS
 TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL FLOORS
 OCCUPIED BY THE DAY CARE OCCUPANCY. DETECTORS ALSO
 SHALL BE INSTALLED IN LOUNGES, RECREATION AREAS AND
 SLEEPING ROOMS IN THE DAY CARE OCCUPANCY.
 436.10.5 SMOKE DETECTION SYSTEMS.
 436.10.5.1
 SINGLE-STATION SMOKE ALARMS INSTALLED IN ACCORDANCE
 WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT REQUIREMENTS
 OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED WITHIN DAY
 CARE HOMES.
 EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN
 ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE
 SAME MANNER SHALL BE PERMITTED.
 436.10.5.2
 WHERE THE DAY CARE HOME IS LOCATED WITHIN A BUILDING OF
 ANOTHER OCCUPANCY, ANY CORRIDORS SERVING THE DAY CARE
 HOME SHALL BE PROVIDED WITH A COMPLETE SMOKE DETECTION
 SYSTEM INSTALLED IN ACCORDANCE WITH NFPA 72.
 436.10.5.3
 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED BY THE
 BUILDING ELECTRICAL SYSTEM.
 436.10.5.4
 SINGLE-STATION SMOKE ALARMS SHALL BE PROVIDED IN ALL
 ROOMS USED FOR SLEEPING.
 436.10.5.5
 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED WITHIN A
 LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA, THEY
 SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM
 SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING UNIT,
 SUITE OF ROOMS OR SIMILAR AREA TO SOUND.
 436.10.5.5.1
 THE ALARMS SHALL SOUND ONLY WITHIN AN INDIVIDUAL LIVING
 UNIT, SUITE OF ROOMS OR SIMILAR AREA AND SHALL NOT
 ACTUATE THE BUILDING FIRE ALARM SYSTEM. REMOTE
 ANNUNCIATION SHALL BE PERMITTED.
  
  
 4) PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING EGRESS IN
 TO THE STRUCTURE, DOORS WITHIN THE STRUCTURE, WINDOW,
 AND OPENING SIZE FOR EACH ROOM THAT WILL HOUSE
 CHILDREN.
 2010 FBC-B 1029.4.1. IN GROUP D OCCUPANCIES SHALL HAVE
 NOT LESS THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE
 THAT COMPLIES WITH THE FOLLOWING:
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 5) 2010 FBC-B 436.6.1 THE FOLLOWING ROOMS OR SPACES
 SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING
 BY FIRE BARRIERS HAVING A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1-HOUR OR SHALL BE PROTECTED BY AN APPROVED
 AUTOMATIC EXTINGUISHING SYSTEM.
 1. BOILER AND FURNACE ROOMS.
 EXCEPTION: ROOMS ENCLOSING ONLY AIR-HANDLING EQUIPMENT.
 2. ROOMS OR SPACES USED FOR THE STORAGE OF COMBUSTIBLE
 SUPPLIES IN QUANTITIES DEEMED HAZARDOUS BY THE BUILDING
 OFFICIAL.
 3. ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS
 MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS IN
 QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
 4. JANITOR CLOSETS.
 EXCEPTION: DOORS TO JANITOR CLOSETS SHALL BE PERMITTED
 TO HAVE VENTILATING LOUVERS WHERE THE SPACE IS
 PROTECTED BY AUTOMATIC SPRINKLERS.
  
 6) 2010 FBC-B 436.6.2 THE FOLLOWING ROOMS OR SPACES
 SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING
 BY FIRE BARRIERS HAVING A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR AND SHALL BE PROTECTED BY AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM.
 1. LAUNDRIES.
 2. MAINTENANCE SHOPS, INCLUDING WOODWORKING AND
 PAINTING AREAS.
 3. ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE BUILDING
 OFFICIAL.
 4. ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
  
 7) 2010 FBC-B 436.10.4 OCCUPANCIES THAT INCLUDE
 PART-DAY PRESCHOOLS, KINDERGARTENS AND OTHER SCHOOLS
 WHOSE PURPOSE IS PRIMARILY EDUCATIONAL EVEN THOUGH THE
 CHILDREN ARE OF PRESCHOOL AGE SHALL COMPLY WITH THE
 PROVISIONS FOR GROUP E OCCUPANCY. IS THERE ANY TEACHING
 OF CHILDREN THAT WILL MAKE TTHE REQUIREMENTS FOR
 EDUCATION APPLY?
  
  
 8) 2010 FL ACCESSIBILITY CODE
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  