| 2013-06-04 16:22:50 | 6-4-13 | | | FIRST REVIEW | | | PLEASE CORRECT PANEL SCHEDULES HP2 AND LP1. THEY BOTH | | | SHOW A FEED TO AHU 1-2 AND CU 1-2. PLEASE REVIEW AND | | | CORRECT. | | | ALSO, CU 1-3 AND 1-4 STATE A MOCP AS 15 AMPS ON THE M | | | DRAWINGS. THERE IS A 20 AMP CIRCUIT BREAKER SHOWN IN | | | THE PANEL SCHEDULE PLEASE CORRECT | | | VB |
|