 FIRST REVIEW:
 1. PLEASE NOTE NEC 210.4.B FOR MULTI BRANCH CIRCUITS TO
 BE SIMULTANEOSLY DISCONNECTED AND 210.4D TO HAVE
 CONDUCTORS GROUPED TOGETHER. (IE; ZIP TIES)
 2. PER 680.22B POOL PUMPS TO HAVE GFCI CIRCUIT BREAKERS
 3. PLEASE REVIEW THE ENTIRE SCOPE FOR THE
 MECHANICAL/ELECTRICAL COORDINATION. IT DOES NOT MATCH.
 EXAMPLES; WHERE IS THE INFO FOR CU1 TO GO WITH AHU1?
 HOW COULD ONE 15A CIRCUIT BREAKER FEED AHU 4A, B AND C?
 THERES MORE. PLEASE REVIEW AND CORRECT.
 VB