| Plan Review Notes For Permit 13050679 |
| Permit Number |
13050679 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-04 15:32:18 | 6-4-13 | | | FIRST REVIEW: | | | 1. PLEASE NOTE NEC 210.4.B FOR MULTI BRANCH CIRCUITS TO | | | BE SIMULTANEOSLY DISCONNECTED AND 210.4D TO HAVE | | | CONDUCTORS GROUPED TOGETHER. (IE; ZIP TIES) | | | 2. PER 680.22B POOL PUMPS TO HAVE GFCI CIRCUIT BREAKERS | | | 3. PLEASE REVIEW THE ENTIRE SCOPE FOR THE | | | MECHANICAL/ELECTRICAL COORDINATION. IT DOES NOT MATCH. | | | EXAMPLES; WHERE IS THE INFO FOR CU1 TO GO WITH AHU1? | | | HOW COULD ONE 15A CIRCUIT BREAKER FEED AHU 4A, B AND C? | | | THERES MORE. PLEASE REVIEW AND CORRECT. | | | VB |
|