| Plan Review Notes For Permit 13050615 |
| Permit Number |
13050615 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-06-21 10:39:05 | **REVISION REQUIRED** | | | | | | **ISSUED AT CONTRACTOR'S RISK** | | | | | | SUBMIT THE FOLLOWING INFORMATION AS A REVISION: | | | | | | 1. COMPLETE INSTALLATION SCHEDULE - ANCHOR SPACING LEFT | | | BLANK | | | | | | 2. SHUTTER CONNECTION MOUNTING TYPE NOT CORRECT; THIS | | | SHOULD CORRELATE WITH THE ANCHOR CHARTS, SEE SHEET 8 OF | | | THE PRODUCT APPROVAL. | | | | | | 3. EMERGENCY MEANS OF ESCAPE NOT SHOWN ON FLOOR PLAN. | | | REVISE FLOOR PLAN TO INCLUDE. FBC R 310.4. | | | | | | |
|