Plan Review Notes
Plan Review Notes For Permit 13050611
Permit Number 13050611
Review Stop E
Sequence Number 1
Notes
Date Text
2013-05-23 13:28:015-23-13
  
 1. SMOKE ALARMS TO BE IN COMPLIANCE WITH THE FLORIDA
 ENERGY CODE SECTION 315 FOR CARBON MONOXIDE PROTECTION
 AND ATTACHED GARAGES
 2. ALL RECETACLES WITHIN SIX FEET OF SINKS TO BE GFCI
 TYPE NEC 210.8
 3. AFCI PROTECTION REQUIRED FOR ALL NEW WIRING
 INSTALLED PER NEC 210.12B
 4. ALL NEW, REPLACED OR RELOCATED RECETACLES MUST BE
 TAMPER RESISTANT PEER NEC 406.11
 VB