Plan Review Notes
Plan Review Notes For Permit 13050586
Permit Number 13050586
Review Stop B
Sequence Number 2
Notes
Date Text
2013-10-19 09:51:48****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. PROVIDE A STRUCTURAL DETAIL FOR PROPOSED
 IMPROVEMENT. SEE FBC 107. PLANS ARE TO INCLUDE WIND
 DESIGN CRITERIA FBC R 301. IF PLANS ARE NOT PREPARED BY
 A DESIGN PROFESSIONAL, CALCULATIONS MAY BE REQUIRED. AS
 NO PLAN WAS SUBMITTED, A COMPLETE CHECKLIST CANNOT BE
 PROVIDED.
  
 PLAN IS TO CLEARLY SHOW MATERIALS AND SCOPE, ALL
 STRUCTURAL CONNECTIONS.
  
 SOME ITEMS INDINCATED AS "METAL"; THIS IS NOT
 SUFFICIENT AS IT DOES NOT PROVIDE A STRENGTH CRITERIA
 OR MATERIAL. OTHER ITEMS SHOW DIMENSION OF 8X4X1, NOT
 CLEAR WHAT THIS MEANS (1 = 1"? NOMINAL?) OR WHAT
 MATERIAL IS PROPOSED. 3" SCREWS ARE SHOWN AS
 CONNECTORS, NOT CLEAR WHAT TYPE OF SCREWS ARE PROPOSED,
 STRENGTH CAPABILITY, OR TYPE.
  
 PLANS REQUIRED - ARCHITECTURAL QUALITY PLAN, FOUNDATION
 PLAN, ELEVATIONS, SECTIONS IF NEEDED. NOT ENOUGH
 INFORMATION TO DETERMINE CODE COMPLIANCE. IF PLANS ARE
 NOT SIGNED AND SEALED BY A DESIGN PROFESSIONAL,
 CALCULATIONS WILL BE REQUIRED FOR ALL SPANS AND
 CONNECTORS.
  
 PLAN DOES NOT INCLUDE WIND DESIGN CRITERIA FBC R 301.
  
 2. SITE PLAN TO SHOW LOCATION OF PROPOSED IMPROVEMENT,
 DIMENSIONS OF IMPROVEMENT, DISTANCE TO PROPERTY LINES,
 AND DISTANCE TO OTHER STRUCTURES, FBC R 302. SITE PLAN
 PROVIDED IS NOT LEGIBLE. IT APPEARS TO SHOW DIMENSIONS
 OF 100' (OR 180'?) X 330', WHICH IS LARGER THAN LOT
 SIZE.
  
 SURVEY NOT CONSISTENT WITH PROPOSED IMPROVEMENT. IS THE
 BRICK AREA TO BE EXTENDED? SEE ORIGINAL COMMENT AND
 PROVIDE ALL INFORMATION FOR BOTH PERGOLA AND ANY OTHER
 WORK TO BE INCLUDED ON THIS PERMIT SUCH AS INCREASE OF
 BRICK AREA. SURVEY FROM 2002 SHOW SCREENED BRICK PATIO
 AND ADJACENT BRICK PATIO AS SAME DIMENSION, SITE PLAN
 PROVIDED APPEARS TO SHOW A REDUCTION IN THE BRICK PATIO
 AND INCREASE IN WHAT WAS FORMERLY CALLED "SCREENED
 BRIUCK PATIO" AREA.
  
 3. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 NOT ADDRESSED.
  
 4. FBC R TABLE 302.1, PROJECTIONS WHICH ARE LESS THAN
 3' FROM THE PROPERTY LINE ARE REQUIRED TO HAVE A 1 HOUR
 FIRE RESISTANCE RATING. IF PROPOSED IMPROVEMENT IS LESS
 THAN 3' FROM PROPERTY LINE, PROVIDE A DETAIL FOR FIRE
 RESISTANCE RATING.
  
 CANNOT DETERMINE COMPLIANCE AS DISTANCE TO PROPERTY
 LINE NOT PROVIDED.
  
 5. VALUE IS TO INCLUDE VALUE OF LABOR AND MATERIALS FBC
 109. FAILURE TO PROVIDE A REASONABLE VALUE MAY CAUSE
 PLAN REVIEW DELAYS. AS SCOPE HAS NOT BEEN SHOWN, IT
 CANNOT BE DETERMINED AT THIS TIME WHETHER OR NOT VALUE
 GIVEN IS REASONABLE.
  
 NOT ADDRESSED. PROVIDE A COST BREAKDOWN AND COMPLETE
 SCOPE FOR THIS PROJECT; NOT CLEAR AT THIS TIME.
  