 1. PROVIDE PANEL SCHEDULE PER NEC 408.4
 2. ALL NEW AND RELOCATED CIRCUITS TO HAVE AFCI
 PROTECTION PER NEC 211.12B
 3. ALL NEW, RELOCATED OR REPLACED RECEPTS TO BE TAMPER
 RESISTANT PER NEC 406.11
 4. ADD SMOKE ALARMS PER RESIDENTIAL CODE SECTIONS 314
 AND 315
 5. ALL ELECTRICAL DEMO CONDUIT AND CONDUCTORS MUST BE
 REMOVED BACK TO ORIGINATION POINT