| 2013-05-20 13:00:56 | BUILDING PLAN REVIEW |
| | PERMIT: 13050574 |
| | ADD: 622 N FLAGLER DR # 901 |
| | CONT: JOSEPH EDWARD KELLY III |
| | TEL: (954)383-5151 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 5/20/2013 |
| | ACTION: DENIED |
| | |
| | 1) THE CONTRACTOR JOSEPH EDWARD KELLY III IS LICENSED |
| | AS A CERTIFIED RESIDENTIAL CONTRACTOR, PLEASE REVIEW |
| | LICENSING DEFINITION FL S 489.105(C) "RESIDENTIAL |
| | CONTRACTOR" MEANS A CONTRACTOR WHOSE SERVICES ARE |
| | LIMITED TO CONSTRUCTION, REMODELING, REPAIR, OR |
| | IMPROVEMENT OF ONE-FAMILY, TWO-FAMILY, OR THREE-FAMILY |
| | RESIDENCES NOT EXCEEDING TWO HABITABLE STORIES ABOVE NO |
| | MORE THAN ONE UNINHABITABLE STORY AND ACCESSORY USE |
| | STRUCTURES IN CONNECTION THEREWITH. THIS IS A HIGH-RISE |
| | BEYOND THE SCOPE OF YOUR LICENSE, " REMODELING, REPAIR, |
| | OR IMPROVEMENT OF ONE-FAMILY, TWO-FAMILY, OR |
| | THREE-FAMILY RESIDENCES"... |
| | |
| | 2) THE CONBTRACTOR INDICATES UNDER SCOPE OF WORK INLAY |
| | WORK OF MARBLE FLOORING BUT THERE IS NO SUBMITTALS FOR |
| | CODE COMPLIANCE FOR THE FOLLOWING CODE REQUIREMENTS; |
| | FBC-B 2010 2010 FBC-B 603.2 |
| | 2A) FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | |
| | 2B) 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3) SHEET 101 INDICATES IN MANY ROOMS NEW CEILING AS |
| | REQUIRED FOR NEW CEILING DESIGN, THE OTHER NOTE ABOUT |
| | CEILING DESIGN IS VERIFY WITH ARCHITECT IN FIELD. |
| | PLEASE PROVIDE THE FRAMING FOR ALL DROPED CEILINGS, |
| | SOFFITS, ETC.. PROVIDE FRAMING TYPE OF MATERIALS, SIZE |
| | OF FRAMING, GAUGE OF FRAMING AND SPACING OF FRAMING AND |
| | IF STIFF BACK WILL BE REQUIRED. PLEASE PROVIDE THE TYPE |
| | OF FASTENERS TO THE DECK ABOVE, AS WELL AS THE TYPE OF |
| | FINISH AND THICKNESS TO BE APPLIED AND AT WHAT THE |
| | FINISH CEILING HEIGHT, OR SOFFIT HEIGHT WILL BE. |
| | 2010 FBC-B TABLE 2506.2STEEL STUDS NON-BEARING ASTM C |
| | 645 & TABLE 2508.1 STEEL FRAMING FOR GYPSUM BOARD. |
| | |
| | 4) SHEET A101 THE NEW DOOR THAT LEADS INTO THE MASTER |
| | BATHROOM IS LABELED A 2'-8" DOOR, THIS WILL PROVIDE A |
| | 30 INCH CLEAR OPENING. PLEASE BE AWARE THIS CONDOMINIUM |
| | IS CONSIDERED UNDER THE FAIR HOUSING REQUIREMENTS, FOR |
| | USABLE DOORS. SEE HINGED DOORS SINGLE LEAF. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |