Plan Review Notes
Plan Review Notes For Permit 13050574
Permit Number 13050574
Review Stop B
Sequence Number 1
Notes
Date Text
2013-05-20 13:00:56BUILDING PLAN REVIEW
 PERMIT: 13050574
 ADD: 622 N FLAGLER DR # 901
 CONT: JOSEPH EDWARD KELLY III
 TEL: (954)383-5151
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/20/2013
 ACTION: DENIED
  
 1) THE CONTRACTOR JOSEPH EDWARD KELLY III IS LICENSED
 AS A CERTIFIED RESIDENTIAL CONTRACTOR, PLEASE REVIEW
 LICENSING DEFINITION FL S 489.105(C) "RESIDENTIAL
 CONTRACTOR" MEANS A CONTRACTOR WHOSE SERVICES ARE
 LIMITED TO CONSTRUCTION, REMODELING, REPAIR, OR
 IMPROVEMENT OF ONE-FAMILY, TWO-FAMILY, OR THREE-FAMILY
 RESIDENCES NOT EXCEEDING TWO HABITABLE STORIES ABOVE NO
 MORE THAN ONE UNINHABITABLE STORY AND ACCESSORY USE
 STRUCTURES IN CONNECTION THEREWITH. THIS IS A HIGH-RISE
 BEYOND THE SCOPE OF YOUR LICENSE, " REMODELING, REPAIR,
 OR IMPROVEMENT OF ONE-FAMILY, TWO-FAMILY, OR
 THREE-FAMILY RESIDENCES"...
  
 2) THE CONBTRACTOR INDICATES UNDER SCOPE OF WORK INLAY
 WORK OF MARBLE FLOORING BUT THERE IS NO SUBMITTALS FOR
 CODE COMPLIANCE FOR THE FOLLOWING CODE REQUIREMENTS;
 FBC-B 2010 2010 FBC-B 603.2
 2A) FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2B) 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3) SHEET 101 INDICATES IN MANY ROOMS NEW CEILING AS
 REQUIRED FOR NEW CEILING DESIGN, THE OTHER NOTE ABOUT
 CEILING DESIGN IS VERIFY WITH ARCHITECT IN FIELD.
 PLEASE PROVIDE THE FRAMING FOR ALL DROPED CEILINGS,
 SOFFITS, ETC.. PROVIDE FRAMING TYPE OF MATERIALS, SIZE
 OF FRAMING, GAUGE OF FRAMING AND SPACING OF FRAMING AND
 IF STIFF BACK WILL BE REQUIRED. PLEASE PROVIDE THE TYPE
 OF FASTENERS TO THE DECK ABOVE, AS WELL AS THE TYPE OF
 FINISH AND THICKNESS TO BE APPLIED AND AT WHAT THE
 FINISH CEILING HEIGHT, OR SOFFIT HEIGHT WILL BE.
 2010 FBC-B TABLE 2506.2STEEL STUDS NON-BEARING ASTM C
 645 & TABLE 2508.1 STEEL FRAMING FOR GYPSUM BOARD.
  
 4) SHEET A101 THE NEW DOOR THAT LEADS INTO THE MASTER
 BATHROOM IS LABELED A 2'-8" DOOR, THIS WILL PROVIDE A
 30 INCH CLEAR OPENING. PLEASE BE AWARE THIS CONDOMINIUM
 IS CONSIDERED UNDER THE FAIR HOUSING REQUIREMENTS, FOR
 USABLE DOORS. SEE HINGED DOORS SINGLE LEAF.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP