2013-10-18 16:40:21THE SUBMITTED DRAWING DOES NOT MEET MINIMUM CODE
 REQUIREMENTS. THE FOLLOWING CORRECTIONS/ADDITIONS SHALL
 BE MADE TO THE DRAWINGS FOR APPROVAL.
 1. BE MORE SPECIFIC AS TO THE SERVICE RISER. IS THE
 INTENT TO SAY THAT EACH UNIT HAS ITS INDIVIDUAL SERVICE
 TYPICAL OF THE ONE SHOWN PLEASE SAT SO.
 2. CIRCUIT DESIGNATION FOR EACH UNIT TO CONFIRM EACH
 A/C SERVICE OUTLET IS SERVED FROM THE CORRESPONDING
 UNIT.
 3. SHOW METER & SERVICE DISCONNECT ON THE EXTERIOR OF
 OF THE FLOOR PLAN
 4. LIVING ROOM SMOKE DETECTOR IN FIRST FLOOR UNIT SHALL
 BE RELOCATED FOR CODE COMPLIANCE.
 5. SHOW EXTERIOR STAIR ILLUMINATION AND SWITCHING TO
 CONFORM WITH FBC
  
 SH CALLED CONTRACTOR TO INFORM HIM OF THESE
 REQUIREMENTS, BUT THERE WAS NO ONE IN THE OFFICE.
 SENT BACK TO BIN R5 BY MA