| Plan Review Notes For Permit 13050533 |
| Permit Number |
13050533 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-23 10:16:31 | 5-23-13 | | | | | | 1. PROVIDE LOAD CALCULATIONS PER NEC 220 | | | 2. FLUORESCENT FIXTURES TO MEET NEC 410.130G | | | 3. LIGHTING CONTROLS REQUIRED PER FLORIDA ENERGY CODE | | | 505.2.2 | | | 4. IDENTIFY DISCONNECTS PER NEC 110.22A | | | 5. PER NEC 210.62, SHOW WINDOW RECEPTACLES ARE REQUIRED | | | FOR EVERY 12 FT OF STORE FRONT | | | VB |
|