2013-06-14 17:41:13RESIDENTIAL (R3) PARTIAL CHANGE OF USE BUILDING REVIEW
 COMMENTS.
 CODE; 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- SHEET A-1: A) ACCORDING TO THE DEFINITION OF BEDROOM
 IN THE 2010 FBC-ENERGY CONSERVATION CODE THIS ROOM IS A
 BEDROOM, NOT A DEN. NEED TO PROVIDE EGRESS WINDOW AS
 REQUIRED BY SEC. R310 OF 2010 FBC-RESIDENTIAL.
  
 B) TYPICAL WALL SECTION: (1) SPECIFY WEEP SCREEDS AS
 REQUIRED BY SEC. R703.6.2 OF 2010 FBC-RESIDENTIAL. (2)
 SPECIFY DOUBLE LAYER OF WATER-RESISTIVE BARRIER OR ANY
 OTHER BOND BRAKE BETWEEN THE STUCCO AND THE WATER
 -RESISTIVE BARRIER AS REQUIRED BY SEC. R703.6.3. OF
 2010 FBC-RESIDENTIAL. (3) SPECIFY ATTIC VENTILATION AS
 REQUIRED BY SEC. R806.
  
 3- NEED TO PROVIDE HEATING TO THE BEDROOM AS REQUIRED
 BY SEC. R303.8 OF 2010 FBC-RESIDENTIAL.
  
 4- SHEET SP-1:
 A) ADDITIONAL FIRE DEPARTMENT NOTES ARE REFERENCING OLD
 CODES. ALSO, THESE NOTES DON'T APPLY TO ONE AND TWO
 FAMILY DWELLINGS. THEY MAY BE DELETED FROM THE DRAWING.
 SEC. 101.2 CITY AMENDMENTS TO FBC.
  
 B) THIS IS A CHANGE OF OCCUPANCY ON ONE AREA OF THE
 BUILDING NOT AN ALTERATION LEVEL 2. REVISE NOTES AS
 REQUIRED. SEC. 406 OF 2010 FBC-EXISTING BUILDING .
  
 5- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.4 AND SEC.
 103.2 OF 2010 FBC-ENERGY CONSERVATION.
  