| 2013-06-14 17:41:13 | RESIDENTIAL (R3) PARTIAL CHANGE OF USE BUILDING REVIEW |
| | COMMENTS. |
| | CODE; 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT |
| | FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| | FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- SHEET A-1: A) ACCORDING TO THE DEFINITION OF BEDROOM |
| | IN THE 2010 FBC-ENERGY CONSERVATION CODE THIS ROOM IS A |
| | BEDROOM, NOT A DEN. NEED TO PROVIDE EGRESS WINDOW AS |
| | REQUIRED BY SEC. R310 OF 2010 FBC-RESIDENTIAL. |
| | |
| | B) TYPICAL WALL SECTION: (1) SPECIFY WEEP SCREEDS AS |
| | REQUIRED BY SEC. R703.6.2 OF 2010 FBC-RESIDENTIAL. (2) |
| | SPECIFY DOUBLE LAYER OF WATER-RESISTIVE BARRIER OR ANY |
| | OTHER BOND BRAKE BETWEEN THE STUCCO AND THE WATER |
| | -RESISTIVE BARRIER AS REQUIRED BY SEC. R703.6.3. OF |
| | 2010 FBC-RESIDENTIAL. (3) SPECIFY ATTIC VENTILATION AS |
| | REQUIRED BY SEC. R806. |
| | |
| | 3- NEED TO PROVIDE HEATING TO THE BEDROOM AS REQUIRED |
| | BY SEC. R303.8 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 4- SHEET SP-1: |
| | A) ADDITIONAL FIRE DEPARTMENT NOTES ARE REFERENCING OLD |
| | CODES. ALSO, THESE NOTES DON'T APPLY TO ONE AND TWO |
| | FAMILY DWELLINGS. THEY MAY BE DELETED FROM THE DRAWING. |
| | SEC. 101.2 CITY AMENDMENTS TO FBC. |
| | |
| | B) THIS IS A CHANGE OF OCCUPANCY ON ONE AREA OF THE |
| | BUILDING NOT AN ALTERATION LEVEL 2. REVISE NOTES AS |
| | REQUIRED. SEC. 406 OF 2010 FBC-EXISTING BUILDING . |
| | |
| | 5- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.4 AND SEC. |
| | 103.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |