| Plan Review Notes For Permit 13050493 |
| Permit Number |
13050493 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-15 18:09:04 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. THIS APPEARS TO BE LOCATED IN EXPOSURE C, SEE FBC R | | | 301.2.1.4.3. PROVIDE MEAN ROOF HEIGHT. FOR 15' MRH, | | | ZONE 3 DP REQUIRED PER FBC R TABLE 301.2(2) IS -95.7; | | | FOR 20' IT IS -102. DESIGN PRESSURE OF -90 PROPOSED | | | DOES NOT COMPLY WITH THE TABLE. | | | | | | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | | FAC9N-3. PROVIDE COVER SHEET FOR THE EVALUATION REPORT. | | | | | | | | | |
|