| 2014-05-15 18:53:26 | THIS PERMIT FAILED THE SECOND ELECTRICAL REVIEW AS |
| | MENTIONED BELOW: |
| | |
| | 1. PER THE FBC-R 314 & 315 YOU SHALL INSTALL |
| | INTER-CONNECTED & BATTERY BACK UP SMOKE/CARBON MONOXIDE |
| | DETECTORS THROUGHOUT THE WHOLE HOUSE AS IF NEW |
| | CONSTRUCTION. ACCORDING TO THE SUBMITTED PLANS, THE |
| | HOUSE CURRENTLY DOES NOT HAVE AND WILL NOT HAVE A |
| | GARAGE. THE ANTICIPATED GARAGE AREA CONTINUES TO BE A |
| | HABITABLE AREA W/A CLOSET; PROBABLE SLEEPING ROOM AND |
| | THEREFORE SMOKE/CARBON MONOXIDE DETECTION AS ABOVE IS |
| | REQUIRED. |
| | 2. ADJUST THE DRAWING SO THAT THE DISCONNECT OR THE |
| | SERVICE OUTLET FOR THE NEW CONDENSING UNIT ARE NOT |
| | BLOCKED BY THE UNIT IN VIOLATION OF NEC 110.26(A). |
| | 3. BOXES USED IN THE CEILING FOR THE FANS OR ANY OTHER |
| | LUMINAIRE SHALL BE LISTED TO SUPPORT A MIN OF 50# AS |
| | STATED IN NEC 314.27. |
| | 4. THE NEW ELECTRICAL PANEL "B" IS INSIDE A WIC IN |
| | VIOLATION OF NEC 240.24(D)&(E). |
| | 5. AS INDICATED IN NEC 210.8(A)(7), THE OUTLETS IN THE |
| | LAUNDRY SHALL BE GFCI PROTECTED. |
| | 6. WHEN "NEW" IS MENTIONED FOR METERS & PANELS "A" &"B" |
| | YOU SHALL INDICATE IF THIS IS A REPLACEMENT FOR AN |
| | OLDER UNIT OR IS THIS A NEW UNIT IN A NEW LOCATION. IF |
| | EXISTING METER AND PANELS ARE ELSEWHERE THAN WHERE |
| | INDICATED ON THE PLANS, THE EXISTING LOCATION SHALL BE |
| | REFLECTED ON THE PLANS. |
| | 7. AS INDICATED BY NEC 230.70 YOU SHALL PROVIDE A |
| | SERVICE DISCONNECT ON THE EXTERIOR OF THE HOME AT A |
| | POINT ADJACENT TO THE METER. |
| | 8. CORRECT THE ELECTRICAL LOAD CALCS AND RISER DIAGRAM |
| | TO INCLUDE THE POOL PANEL AND IT'S RESPECTIVE LOAD. LET |
| | THE CORRECTED RISER DIAGRAM REFLECT THE REQUIRED |
| | DISCONNECTS ON THE EXTERIOR OF THE HOME. |
| | NOTE: YOU WILL NOT NEED TO USE A MAIN BREAKER PANEL |
| | WHEN THE MAINS ARE OUTSIDE. YOU CAN GET BY WITH A MAIN |
| | LUG ONLY. |
| | |
| | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL |
| | PLANS EXAMINER |
| | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| | FOLLOWING LINK: |
| | |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX |
| | |
| | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| | ABOVE THE SECOND PERMIT INFORMATION). |
| | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER |
| | PERMIT CONDITIONS. |
| | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |