2014-05-15 18:53:26THIS PERMIT FAILED THE SECOND ELECTRICAL REVIEW AS
 MENTIONED BELOW:
  
 1. PER THE FBC-R 314 & 315 YOU SHALL INSTALL
 INTER-CONNECTED & BATTERY BACK UP SMOKE/CARBON MONOXIDE
 DETECTORS THROUGHOUT THE WHOLE HOUSE AS IF NEW
 CONSTRUCTION. ACCORDING TO THE SUBMITTED PLANS, THE
 HOUSE CURRENTLY DOES NOT HAVE AND WILL NOT HAVE A
 GARAGE. THE ANTICIPATED GARAGE AREA CONTINUES TO BE A
 HABITABLE AREA W/A CLOSET; PROBABLE SLEEPING ROOM AND
 THEREFORE SMOKE/CARBON MONOXIDE DETECTION AS ABOVE IS
 REQUIRED.
 2. ADJUST THE DRAWING SO THAT THE DISCONNECT OR THE
 SERVICE OUTLET FOR THE NEW CONDENSING UNIT ARE NOT
 BLOCKED BY THE UNIT IN VIOLATION OF NEC 110.26(A).
 3. BOXES USED IN THE CEILING FOR THE FANS OR ANY OTHER
 LUMINAIRE SHALL BE LISTED TO SUPPORT A MIN OF 50# AS
 STATED IN NEC 314.27.
 4. THE NEW ELECTRICAL PANEL "B" IS INSIDE A WIC IN
 VIOLATION OF NEC 240.24(D)&(E).
 5. AS INDICATED IN NEC 210.8(A)(7), THE OUTLETS IN THE
 LAUNDRY SHALL BE GFCI PROTECTED.
 6. WHEN "NEW" IS MENTIONED FOR METERS & PANELS "A" &"B"
 YOU SHALL INDICATE IF THIS IS A REPLACEMENT FOR AN
 OLDER UNIT OR IS THIS A NEW UNIT IN A NEW LOCATION. IF
 EXISTING METER AND PANELS ARE ELSEWHERE THAN WHERE
 INDICATED ON THE PLANS, THE EXISTING LOCATION SHALL BE
 REFLECTED ON THE PLANS.
 7. AS INDICATED BY NEC 230.70 YOU SHALL PROVIDE A
 SERVICE DISCONNECT ON THE EXTERIOR OF THE HOME AT A
 POINT ADJACENT TO THE METER.
 8. CORRECT THE ELECTRICAL LOAD CALCS AND RISER DIAGRAM
 TO INCLUDE THE POOL PANEL AND IT'S RESPECTIVE LOAD. LET
 THE CORRECTED RISER DIAGRAM REFLECT THE REQUIRED
 DISCONNECTS ON THE EXTERIOR OF THE HOME.
 NOTE: YOU WILL NOT NEED TO USE A MAIN BREAKER PANEL
 WHEN THE MAINS ARE OUTSIDE. YOU CAN GET BY WITH A MAIN
 LUG ONLY.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.