| Plan Review Notes For Permit 13050465 |
| Permit Number |
13050465 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-21 09:06:07 | 5-21-13 | | | | | | NOTE: ALL ELECTRIC PER THE 2008 NEC | | | | | | 1. GARAGE DOOR OPENER TO BE GFI TYPE. ALL GARAGE | | | RECEPTS REQUIRE GFI. THERE ARE NO EXCEPTIONS LISTED IN | | | THE NEC | | | 2. ALL RECEPTS TO BE TAMPER RESISTANT TYPE PER NEC | | | 406.11 | | | 3. BATHROOM WHIRLPOOL TUB TO BE BONDED PER NEC 680.74 | | | 4. PLEASE CLARIFY PANEL SCHEDULE REGARDING AC#2. BOTH | | | 2/4 AND 6/8 ARE LABELED THE SAME. ALSO, PLEASE PROVIDE | | | AC EQUIPMENT SCHEDULE SHOWING | | | NECESSARY ELECTRICAL DATA TO COMPARE WITH CIRCUIT | | | BREAKER SIZING. ALSO, THE TERM "GENERAL LIGHTING" DOES | | | NOT MEET NEC 406.4. CIRCUITS MUST BE MARKED FOR THEIR | | | CLEAR, EVIDENT AND SPECIFIC PURPOSE. | | | 5. BALANCE OF HOME MUST ALSO HAVE SMOKE ALARMS INSALLED | | | PER RESIDENTIAL CODE 314/315 IF NOT EXISTING WHETHER | | | WORK IS DONE IN THESE AREAS OR NOT. | | | 6. PLEASE CHANGE ELECRICAL NOTE 32 FROM "BEDROOMS" TO | | | "ALL AREAS" PER NEC 210.12B | | | VB | | | |
|