Plan Review Notes
Plan Review Notes For Permit 13050465
Permit Number 13050465
Review Stop E
Sequence Number 1
Notes
Date Text
2013-05-21 09:06:075-21-13
  
 NOTE: ALL ELECTRIC PER THE 2008 NEC
  
 1. GARAGE DOOR OPENER TO BE GFI TYPE. ALL GARAGE
 RECEPTS REQUIRE GFI. THERE ARE NO EXCEPTIONS LISTED IN
 THE NEC
 2. ALL RECEPTS TO BE TAMPER RESISTANT TYPE PER NEC
 406.11
 3. BATHROOM WHIRLPOOL TUB TO BE BONDED PER NEC 680.74
 4. PLEASE CLARIFY PANEL SCHEDULE REGARDING AC#2. BOTH
 2/4 AND 6/8 ARE LABELED THE SAME. ALSO, PLEASE PROVIDE
 AC EQUIPMENT SCHEDULE SHOWING
 NECESSARY ELECTRICAL DATA TO COMPARE WITH CIRCUIT
 BREAKER SIZING. ALSO, THE TERM "GENERAL LIGHTING" DOES
 NOT MEET NEC 406.4. CIRCUITS MUST BE MARKED FOR THEIR
 CLEAR, EVIDENT AND SPECIFIC PURPOSE.
 5. BALANCE OF HOME MUST ALSO HAVE SMOKE ALARMS INSALLED
 PER RESIDENTIAL CODE 314/315 IF NOT EXISTING WHETHER
 WORK IS DONE IN THESE AREAS OR NOT.
 6. PLEASE CHANGE ELECRICAL NOTE 32 FROM "BEDROOMS" TO
 "ALL AREAS" PER NEC 210.12B
 VB
  