| Plan Review Notes For Permit 13050389 |
| Permit Number |
13050389 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-14 12:16:23 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | SEE 803, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | | E-84. | | | | | | IF A DIFFERENT TEST IS USED, THIS IS TO BE SUBMITTED | | | UNDER ALTERNATIVE MATERIALS AND METHODS, FBC 104.11. | | | SUPPORTING DOCUMENTATION/ANALYSIS TO BE SUBMITTED. | | | | | | THE PRODUCT PROPOSED WAS TESTED USING DOC-FF-1-70. TO | | | USE THIS STANDARD, IT MUST BE DEMONSTRATED THAT THIS | | | MEETS OR EXCEEDS MINIMUM CODE REQUIREMENTS. | | | | | | | | | |
|