| Plan Review Notes For Permit 13050344 |
| Permit Number |
13050344 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-13 16:27:10 | BUILDING PLAN REVIEW | | | PERMIT: 13050344 | | | ADD: 140 PAMELA LANE | | | CONT: TIM GRABOSKI ROOFING | | | TEL: (561)286-8252 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: 5/13/2013 | | | ACTION: DENIED | | | | | | 1) MIAMI-DADE NOA 08-0410.09 | | | PAGE 35 OF 38 CIRCLED | | | SYSTEM TYPE E(6) BASE SHEET MECHANICALLY FASTENED | | | DECK TYPE 1: WOOD , NON-INSULATED | | | | | | MAXIMUM DESIGN PRESSURE -60 PSF (SEE GENERAL LIMITATION | | | # 7) | | | | | | FASTENER DENITIES SHALL BE INCREASED FOR BOTH | | | INSULATION & BASE SHEET AS CALCULATED IN COMPLIANCE | | | WITH ROOF ING APPLICATION STANDARD RAS 117. | | | CALCULATIONS PREPARED BY EITHER A ARCHITECT OR | | | ENGINEER. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | |
|