| Plan Review Notes For Permit 13050323 |
| Permit Number |
13050323 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-20 15:00:17 | 5-20-13 | | | 1. LIGHTING CONTROLS ARE REQUIRED PER FLORIDA ENERGY | | | CODE SECTION 505. (BUILDINGS OVER 5000 SQ FT) | | | 2. BECAUSE THE EXISTING FIXTURES ARE BEING REWORKED AND | | | REUSED, THEY MUST HAVE A DISCONNECT MEANS FIELD | | | INSTALLED TO COMPLY WITH NEC 410.130G | | | 3. ADD ONE LINE ELECTRICAL RISER DIAGRAM PER NEC 215.5 | | | 4. CIRCUITS BEING RUN MUST COMPLY TO NEC 210.4 IF | | | UTILIZING MULTI BRANCH WIRING METHODS. | | | VB | | 2013-05-20 14:56:15 | 5-20-13 |
|