Plan Review Notes
Plan Review Notes For Permit 13050323
Permit Number 13050323
Review Stop E
Sequence Number 1
Notes
Date Text
2013-05-20 15:00:175-20-13
 1. LIGHTING CONTROLS ARE REQUIRED PER FLORIDA ENERGY
 CODE SECTION 505. (BUILDINGS OVER 5000 SQ FT)
 2. BECAUSE THE EXISTING FIXTURES ARE BEING REWORKED AND
 REUSED, THEY MUST HAVE A DISCONNECT MEANS FIELD
 INSTALLED TO COMPLY WITH NEC 410.130G
 3. ADD ONE LINE ELECTRICAL RISER DIAGRAM PER NEC 215.5
 4. CIRCUITS BEING RUN MUST COMPLY TO NEC 210.4 IF
 UTILIZING MULTI BRANCH WIRING METHODS.
 VB
2013-05-20 14:56:155-20-13