| Plan Review Notes For Permit 13050312 |
| Permit Number |
13050312 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-30 12:15:38 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROVIDE A COPY OF THE CONTRACT, FBC 109. A COST | | | BREAKDOWN MAY BE REQUIRED. | | | | | | 2. CLARIFY SCOPE. APPLICATION IS FOR "BUS SHELTER" | | | (SINGULAR) BUT TWO ARE SHOWN ON THE SITE PLAN. | | | | | | 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | THE ROOF, FAC9N-3, FBC 1609. | | | | | | 4. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC | | | 1604.3.1, INCLUDING COMPONENT & CLADDING PRESSURES FOR | | | THE ROOF. | | | | | | 5. ROOF PRODUCT APPROVAL TO BE REVIEWED BY DESIGNER OF | | | RECORD FBC 107. | | | | | | 6. ON THE ROOF PRODUCT APPROVAL, INDICATE METHOD OF | | | FASTENING PROPOSED. | | | | | | 7. ADVISORY ONLY, SEPARATE ROOF SUB PERMIT WILL BE | | | REQUIRED. | | | |
|