Plan Review Notes
Plan Review Notes For Permit 13050282
Permit Number 13050282
Review Stop E
Sequence Number 1
Notes
Date Text
2013-05-17 16:23:25RECPT FOR GDO SHOULD BE GFI PER NEC 210.8.A.2. THERE
 ARE NO EXCEPTIONS LISTED
 COMBINATION SMOKE/ CO DETECTORS REQUIRED PER R315 OF
 THE FBC
 SMOKE/CO DETECTOR REQUIRED AT TOP AND BOTTOM OF STAIRS
 AFCI PROTECTION REQUIRED PER NEC 210.12B
 VB