 PERMIT #13050227
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 FIRE LANES/ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
 THE NORTH 20" X 20" CONCRETE BAR CODE READER IMPINGES
 UPON THIS CLEAR WIDTH.
  
 ALL GATES: PROVIDE A KNOX KEY SWITCH TO ALLOW GATE
 ACCESS TO EMERGENCY RESPONDERS. KEY SWITCH CAN BE
 ORDERED FROM WWW.KNOXBOX.COM. BOTH GATE SECTIONS SHALL
 OPEN SIMULTANEOUSLY TO PROVIDE AT LEAST 20 FEET OF
 UNOBSTRUCTED FIRE DEPARTMENT ACCESS.
  
 THE REMOVAL OF THE PAVEMENT NORTHEAST OF THE POOL AREA
 APPEARS TO CREATE A 250 FOOT (APPROX.) VEHICLE DEAD-END
 FOR THE ADJACENT APARTMENT BUILDING. DEAD-END FIRE
 DEPARTMENT ACCESS ROADS IN EXCESS OF 150 FEET IN LENGTH
 SHALL BE PROVIDED WITH APPROVED PROVISIONS FOR THE FIRE
 APPARATUS TO TURN AROUND.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  