| Plan Review Notes For Permit 13050203 |
| Permit Number |
13050203 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-14 08:46:38 | 5-14-13 | | | | | | 1 PROVIDE PANEL DIRECTORY WITH UPDATED INFORMATION PER | | | NEC 408.4.A | | | | | | 2. ADD NOTE TO DRAWING - ALL ELECTRIC TO MEET 2008 NEC | | | | | | 3. SHOW CIRCUITRY ON DRAWINGS | | | | | | 4. ADD THE FOLLOWINT NOTES: | | | A. ALL NEW RECEPTS TO BE TAMPER RESISTANT PER NEC | | | 406.11 | | | B. ALL NEW WIRING MUST BE PROTECTED WITH AFCI BREAKERS | | | PER NEC 210.12.B | | | | | | 5. SHOW SMOKE ALARMS PE FBC RESIDENTIAL 314.3.1 | | | | | | 6. SHOW "NEW" AND "EXISTING" DEVICES ON PLAN | | | | | | VB |
|