| Plan Review Notes For Permit 13050197 |
| Permit Number |
13050197 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-14 09:29:58 | 5-14-13 | | | | | | 1. ALL ELECTRIC TO MEET 2008 NEC | | | 2. ALL NEW RECEPTS TO BE TAMPER RESISTANT PER NEC | | | 406.11 | | | 3. SHOW "NEW" AND "EXISTING" DEVICES ON DRAWINGS | | | 4. INSTALL AFCI BREAKERS PER NEC 210.12B | | | 5. SMOKE ALARMS AS REQUIRED BY RBC 315 MUST HAVE CO | | | PROTECTION AS WELL AS SMOKE. | | | 6. NEC TABLE 310.15 B6 SHOWS CONDUCTORS TO A 150A | | | SERVICE TO BE #1, NOT #2 | | | VB |
|