| Plan Review Notes For Permit 13050197 |
| Permit Number |
13050197 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-17 13:31:59 | RESIDENTIAL (R3) RENOVATIONS, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 101.4 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) WINDOW MULLIONS, INCLUDING WINDOW MULLIONS FOR BAY | | | WINDOW IN DINING AREA. | | | | | | B) ROOF RIDGE VENT. | | | | | | C) FLAT ROOF. NOA 12-0227.18 SUBMITTED WAS SUPERSEDED | | | BY MIAMI-DADE. VISIT THE MIAMI DADE WEBSITE AND | | | DOWNLOAD CURRENT NOA. | | | AND, PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 TO MEET THE DESIGN PRESSURES OF SEC. | | | R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | | | | ***NOTE: IF NOA SUBMITTED REQUIRES RAS 117 CALCULATIONS | | | TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED AND SEALED | | | RAS 117 CALCULATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|